The drive has lost communication with the fieldbus network due to a timeout condition. The manual's first action is: “Check for and correct: • Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). • Communication settings (Group 51 or 53 as appropriate). • Poor connections and/or noise on line.”
- Model
- ABB ACH550
- Display shows
- I/O COMM (2005)
- Type
- Fault code
- Source
- Manual p. 29
What 2005 means
I/O COMM p. 29
Common causes
- Fieldbus communication has timed out. p. 29
What to do
- Check for and correct: • Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). • Communication settings (Group 51 or 53 as appropriate). • Poor connections and/or noise on line. p. 29
Before you service the product, read the safety instructions in the manual p. 2.
If 2005 is still not resolved
- contact the factory or your local Authorized Service Center for repair or replacement. p. 2 “Never attempt to repair a malfunctioning ACH550; contact the factory or your local Authorized Service Center for repair or replacement.”
This page summarises what the manufacturer’s manual says about 2005; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.