Fault code1013
PAR PFA IO 2 means the actual number of PFA motors does not match those configured in Group 14 or the autochange interval parameter. The manual lists no action for this code.
- Model
- ABB ACH550
- Display shows
- PAR PFA IO 2 (1013)
- Type
- Fault code
- Source
- Manual p. 28
What 1013 means
PAR PFA IO 2 p. 28
Common causes
- IO configuration is not complete – the actual number of PFA motors (parameter 8127, MOTORS) does not match the PFA motors in Group 14 and parameter 8118 AUTOCHNG INTERV. p. 28
If 1013 is still not resolved
- contact the factory or your local Authorized Service Center for repair or replacement. p. 2 “Never attempt to repair a malfunctioning ACH550; contact the factory or your local Authorized Service Center for repair or replacement.”