ABB ACH550 Error 2001: OVERCURRENT

AC drive · taken from the manufacturer’s manual, pages cited

Fault code2001

The drive has detected excessive current flow due to the current limiting controller being active. The manual's first action is: “Check for and correct: • Excessive motor load. • Insufficient acceleration time (parameters 2202 ACCELER TIME 1 and 2205 ACCELER TIME 2). • Faulty motor, motor cables or connections. • Output disconnect device not interlocked. • Interaction with external input filter.”

Model
ABB ACH550
Display shows
OVERCURRENT (2001)
Type
Fault code
Source
Manual p. 29

What 2001 means

OVERCURRENT p. 29

Common causes

  • Current limiting controller is active. p. 29

What to do

  1. Check for and correct: • Excessive motor load. • Insufficient acceleration time (parameters 2202 ACCELER TIME 1 and 2205 ACCELER TIME 2). • Faulty motor, motor cables or connections. • Output disconnect device not interlocked. • Interaction with external input filter. p. 29

Before you service the product, read the safety instructions in the manual p. 2.

If 2001 is still not resolved

  • contact the factory or your local Authorized Service Center for repair or replacement. p. 2
    “Never attempt to repair a malfunctioning ACH550; contact the factory or your local Authorized Service Center for repair or replacement.”