Kutai CM0900 Automatic Transfer Switch Control Unit Operator's Manual
This manual provides instructions for installing, operating, and programming the Kutai CM0900 Automatic Transfer Switch Control Unit. It details hardware components, panel controls, and wiring diagrams. The unit monitors power sources and controls transfer between normal and standby power, with adjustable time delays and voltage sensing. It is designed for use with 1Ø 220V systems and includes features like auto/test pushbutton, LEDs, and external exerciser terminals.
Read onlineKutai CM0900 specifications
| Operating Voltage | 160 VAC to 270 VAC |
|---|---|
| Time Delay Normal to Emergency (TDNE) | 2, 10, 20, 30 seconds |
| Time Delay Engine Start (TDES) | 2, 5, 10, 15 seconds |
| Time Delay Emergency to Normal (TDEN) | 2, 10, 120, 300 seconds |
| Time Delay Engine Cool-down (TDEC) | 2, 30, 120, 300 seconds |
| Over Voltage Setting | 270VAC |
| Under Voltage Setting | 180VAC |
Source: Kutai CM0900 Automatic Transfer Switch Control Unit Operator's Manual
All Kutai CM0900 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What voltage range does the CM0900 controller support?
The CM0900 controller operates with system voltage from 160 VAC to 270 VAC at 50 or 60 Hz.
From: Kutai CM0900 Automatic Transfer Switch Control Unit Operator's Manual
How does the CM0900 controller handle power transfer?
The CM0900 controller monitors power sources and transfers between normal and standby power based on preset voltage thresholds and time delays.
From: Kutai CM0900 Automatic Transfer Switch Control Unit Operator's Manual
What is the operating voltage range for the CM0900 module?
The module operates on a voltage range of 160 to 280VAC at 50/60Hz.
From: Kutai CM0900 Single-Phase 220V ATS Control Module User Manual
What are the adjustable delay times for the engine start function?
The engine start delay (TDES) can be set to 2, 5, 10, or 15 seconds.
From: Kutai CM0900 Single-Phase 220V ATS Control Module User Manual