Kutai EA16 Generator Automatic Voltage Regulator Operation Manual
This manual provides instructions for installing, adjusting, and troubleshooting the Kutai EA16 Automatic Voltage Regulator. It details terminal connections, voltage and frequency settings via DIP switches, and adjustment of output voltage and droop using potentiometers. Safety precautions are emphasized, including heat sink handling and fuse specifications. Troubleshooting tables address common issues like low residual voltage or unstable output.
The EA16 is designed for 170–510 VAC brushless generators with paralleling compatibility, featuring enhanced safety circuits and optional PLC control inputs for advanced applications.
Kutai EA16 specifications
| Sensing Input Voltage | 170 ~ 510 VAC, Single Phase 2 wires |
|---|---|
| Output Voltage | Max. 90 VDC @ 240 VAC input |
| Current Continuous | 16A |
| Voltage Regulation | < ± 0.5% ( with 4% engine governing ) |
| Dimensions | 156mm L * 106mm W * 43mm H |
| Weight | 450g ± 2% |
Source: Kutai EA16 Generator Automatic Voltage Regulator Operation Manual
All Kutai EA16 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What voltage range does the EA16 AVR support?
It supports 170–510 VAC for sensing input, selectable via DIP switch for 220V or 440V systems.
From: Kutai EA16 Generator Automatic Voltage Regulator Operation Manual
How do I adjust the output voltage?
Use the DIP switch to select voltage range, then adjust the external voltage trim potentiometer (VR1, VR2) for ±5% adjustment.
From: Kutai EA16 Generator Automatic Voltage Regulator Operation Manual
What is the fuse specification for the EA16-400Hz AVR?
The fuse specification is 16A / 250V slow blow type.
From: Kutai EA16-400Hz Generator Automatic Voltage Regulator Operation Manual
How do you perform field flashing if residual voltage is low?
Stop the generator, disconnect field wires, apply DC voltage using a battery with a 3~5 ohm 20 watt resistor, wait 3 seconds, remove the battery, and restart the generator.
From: Kutai EA16-400Hz Generator Automatic Voltage Regulator Operation Manual