JTPLC DDM5A1 Digital Display Table Datasheet
The DDM5A1 digital display table is designed for use with programmable logic controllers (PLC), DCS, computers and other control and acquisition systems to show parameters such as temperature, pressure, flow, speed, angle, position, quantity, frequency, voltage, current, time and fault codes. It supports RS‑485 communication (up to 32 devices) and optional RS‑232 via a converter.
The module features a 5‑digit 0.8" LED display with optional sign, 15 special symbols, 10‑segment bar‑graph display, programmable decimal point, and polarity protection. It operates from a 4.8‑5.5 V DC supply, consumes up to 300 nW, and can be mounted in any orientation. This manual is written in Chinese.
JTPLC DDM5A1 specifications
| Working voltage | DC 4.8‑5.5 V |
|---|---|
| Power consumption | Maximum 300 nW |
| Interface signal | Two‑wire half‑duplex RS‑485 |
| Communication speed | Selectable (e.g., 9600 bps) |
| Transmission distance | < 1200 m |
| Refresh speed | > 20 ns |
| Display accuracy | Matches PLC internal data exactly |
| Dimensions (W×H×D) | 160 mm × 76 mm × 65 mm |
| Weight (without packaging) | ≈ 0.20 kg |
| Operating humidity | 35 %‑85 % RH |
| Maximum number of devices on RS‑485 bus | 32 |
All JTPLC DDM5A1 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Ratings, dimensions and ordering codes, for selection and design work.
Questions answered in these manuals
How is the device address set on the DDM5A1?
The address is stored in register B5; for example, setting DB5=H3130 (CB5H=30H) assigns the slave address 01.
How many display modules can be networked together?
Up to 32 DDM5A1 modules can be connected on a single RS‑485 network.