Autonics TX4S Series PID Temperature Controller User Manual
This manual explains how to install and safely operate the Autonics TX4S Series PID Temperature Controller. It includes safety considerations, mounting instructions, wiring recommendations, and guidelines for avoiding hazards such as electric shock and fire.
The document details the controller’s specifications, input sensor options, control and alarm output types, RS485 Modbus communication settings, and parameter configuration procedures such as auto‑tuning, hysteresis, and alarm options. Troubleshooting tips and a Modbus mapping table are also provided.
Autonics TX4S Series specifications
| Power supply | 100-240VAC 50/60Hz |
|---|---|
| Power consumption | Max. 8VA |
| Input type | RTD DPt100Ω, Cu50Ω; TC K(CA), J(IC), L(IC), T(CC), R(PR), S(PR) |
| Display method | 11 segments (PV: white, SV: green), other display (yellow) with LCD method |
| PV character size | 6.9×15.3mm |
| Relay output | 250VAC 3A 1a |
| SSR drive output | Max. 12VDC ± 2V 20mA |
| Control method | ON/OFF control, P, PI, PD, PID control |
| Sampling period | 50ms |
| Communication output | RS485 Communication output (Modbus RTU method) |
| Protection structure | IP50 (front panel, IEC standards) |
| Weight | Approx. 135.2g (approx. 85.2g) |
Source: Autonics H-18TX4S Series LCD Display PID Temperature Controller
All Autonics TX4S Series documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What is the sampling period of the H-18TX4S Series temperature controller?
The sampling period is 50 ms.
From: Autonics H-18TX4S Series LCD Display PID Temperature Controller
Which temperature sensors can the controller accept?
It accepts RTD Pt100Ω and Cu50Ω sensors, as well as K, J, L, T, R and S thermocouples.
From: Autonics H-18TX4S Series LCD Display PID Temperature Controller
What power supply voltage range should be used for the TX4S controller?
The controller requires a power supply of 100‑240VAC at 50/60 Hz, and the allowable voltage range is 90 % to 110 % of the rated voltage.
From: Autonics TX4S Series PID Temperature Controller User Manual
How can the controller be connected to a PC for parameter setting?
Use the PC loader port with an EXT‑US converter cable (sold separately) and a SCM‑US USB‑to‑Serial converter (sold separately) to communicate with DAQMaster software on the PC.
From: Autonics TX4S Series PID Temperature Controller User Manual
What display does the TX4S use?
An easy-to-read LCD display with large 15.3mm characters.
From: Autonics TX4S Series Temperature Controller Instruction Manual
What is the sampling cycle?
A 50ms high-speed sampling cycle.
From: Autonics TX4S Series Temperature Controller Instruction Manual