User manual for the Zhongchuang Zhihe ZH-4041 three-phase electrical parameter collector, covering specifications, wiring, and Modbus communication.
The Zhongchuang Zhihe ZH-4041 is a three-phase electrical parameter collector for measuring AC three-phase circuits, and it can also be used for three single-phase circuits. It uses a high-precision 24-bit dedicated AD chip and provides RS485 or Ethernet RJ45 communication with selectable Modbus-RTU or Modbus-TCP protocol.
The manual documents product variants, performance specifications, dimensions and pin definitions, wiring examples, and Modbus register definitions for reading and writing electrical parameters. This manual is written in Chinese.
| Input wiring | Three-phase four-wire / three-phase three-wire (or three single-phase circuits) |
|---|---|
| Accuracy | Voltage/current 0.2%; power better than 0.5% |
| Current range | 10mA, 100mA, 1A, 5A, 10A, 30A, 50A, 100A AC |
| Voltage range | 10V, 100V, 250V, 400V, 500V AC |
| Voltage input impedance | 2 kΩ/V |
| Frequency response | 30 Hz to 1.2 kHz |
| Operating temperature | -20°C to +60°C |
| Temperature drift | ≤100 ppm/°C |
| RMS update time | 20, 40, 60, 80, 100 (default), 400, 1000 ms |
| Isolation voltage | >2500 VDC |
| Auxiliary power | +10 to +30 VDC, +10 to +55 VDC, or 85 to 265 VAC |
| Rated power consumption | <2 W |
| Communication baud rates | 4800, 9600, 19200, 38400, 57600, 115200 bps |
| Data format | No/odd/even parity, 8 data bits, 1 stop bit; or no parity, 9 data bits |
| Default settings | Address 1, 9600 baud, no parity, 8 data bits, 1 stop bit |
| AD converter | High-precision 24-bit dedicated AD chip |
| Surge withstand | Input, output, and power ports withstand surge voltage above 2 kV |
| Sampling periods | 20, 40, 60, 80, 100, 400, 1000 ms |
| Power supply options | DC 10-30 V, 10-55 V, or AC/DC 85-265 V |
| Through-hole diameter | 7.5 mm |
The default settings are address 1, baud rate 9600, no parity, 8 data bits, and 1 stop bit.
The device supports three-phase four-wire, three-phase three-wire, or three single-phase circuits.
It supports RS485 or Ethernet RJ45 interfaces and Modbus-RTU or Modbus-TCP protocols.
Use an external current transformer; currents above 5 A use through-hole input.
Use a 400 ms data update time for better stability.