Zhongchuang Zhihe ZH-4041-3 Network Three-Phase Power Parameter Collector User Manual

User manual for the Zhongchuang Zhihe ZH-4041-3 network three-phase electrical parameter collector: models, specs, wiring and Modbus registers.


Zhongchuang Zhihe ZH-4041-3 Network Three-Phase Power Parameter Collector User Manual - cover page
Brand
中创智合
Category
Voltage and Current Measurement
Document type
User Manual
Language
Chinese
Pages
15
File format
PDF
File size
1.3 MB
Published
09 November, 2026
Updated
09 November, 2026
MD5 checksum
192D84EFF4F91139A4968DAB382D76D9

About this manual

This is the user manual (使用说明书) for the Zhongchuang Zhihe ZH-4041-3 network three-phase electrical parameter collector, a three-phase isolated measuring instrument that can also measure three single-phase circuits. It uses a 24-bit AD chip, measures true RMS values of phase and line voltage, current, frequency, active and reactive power, power factor, harmonic power and accumulated energy, and communicates over RS485 or Ethernet RJ45 (or Wifi) using Modbus-RTU or Modbus-TCP.

The document covers the product overview and feature list, the model numbering (ZH-4041-34N1, ZH-4041A-34N1, ZH-4041-35N1, ZH-4041A-35N1, ZH-4041-39N1, ZH-4041A-39N1, plus a -6 Wifi suffix), performance specifications, outline and pin definitions, wiring diagrams for three-phase four-wire, three-phase three-wire (two-meter and three-meter) and single-phase use, and the Modbus-RTU and Modbus-TCP message formats with register definitions. This manual is written in Chinese.

What's inside

  • 产品概述
  • 产品型号
  • 性能指标
  • 产品外形结构图与引脚定义
  • 产品接线图
  • MODBUS通讯协议
  • 寄存器说明与命令格式

Specifications

输入接线方式三相四线/三相三线(或三个单相回路)
精度等级电压电流 0.2%;功率综合优于 0.5%
电流量程10mA, 100mA, 1A, 5A, 10A, 30A, 50A, 100A AC (above 5A uses through-hole type, 7.5mm)
电压量程10V, 100V, 250V, 400V, 500V AC
电压输入阻抗2KΩ/V
频率响应30Hz-1.2KHz
工作温度-20℃ to +60℃
隔离耐压>2500VDC
辅助电源+10V~+30VDC or +10V~+55VDC or 85~265VAC
额定功耗<2W
通讯波特率4800, 9600, 19200, 38400, 57600, 115200bps
数据更新时间20ms, 40ms, 60ms, 80ms, 100ms (default), 400ms, 1000ms

Frequently asked questions

What are the factory default RS485 communication settings?

Address 1, baud rate 9600, no parity, 8 data bits and 1 stop bit.

What is the factory IP address and port of the RJ45 network port?

The factory IP is 192.168.2.7 and the port number is 20108; the web login user name and password are both admin.

Which communication protocols does the device support?

Modbus-RTU or Modbus-TCP can be selected; the factory default protocol is Modbus-RTU and switching to Modbus-TCP requires a protocol setting per register 0060H.

What must be configured for three-phase three-wire (two-meter) wiring?

The module measurement mode must be set to the three-phase three-wire mode in register 0056H (86).

What sampling time should be used for variable-frequency signals?

A 400ms sampling time should be used for better stability.