User manual for the Zhongchuang Zhihe ZH-40243-14F2 24-channel AC current and voltage acquisition module with RS485 Modbus-RTU.
The Zhongchuang Zhihe ZH-40243-14F2 is a 24-channel data acquisition module for AC current or voltage, with mixed current and voltage input supported. It uses high-precision current/voltage transformers and a true RMS measurement chip, and communicates over RS485 using the Modbus-RTU protocol.
The manual covers product overview, model variants, performance specifications, appearance and installation dimensions, wiring instructions, and Modbus communication protocol details including register definitions and command examples. Applications mentioned include street-light monitoring, production automation testing, and LED lamp aging testing. This manual is written in Chinese.
| Channels | 24 |
|---|---|
| Measurement type | AC current or voltage; mixed input supported |
| Accuracy | 0.2% |
| AC current ranges | 0-10 mA / 100 mA / 0-1 A / 0-5 A AC |
| AC voltage ranges | 0-10 V / 100 V / 300 V / 450 V AC |
| Input impedance | Voltage channels: 2 kΩ/V; current channels: 0 Ω |
| Operating temperature | -20°C to +60°C |
| Data update time | 100 ms default; settable to 80, 60, 40, 20, 400, 1000 ms |
| Isolation withstand voltage | >2500 VDC |
| Auxiliary power | +9 to +30 VDC or +9 to +55 VDC (model dependent) |
| Power consumption | <2 W (typical 24 V supply <40 mA) |
| Communication interface | RS485, Modbus-RTU, bus load up to 255 devices |
| Baud rates | 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps |
| Data format | Odd/even/no parity (default no parity), 8 data bits, 1 stop bit |
| Dimensions | 217 x 112 x 47 mm |
| Screw mounting dimensions | 198.2 x 98 mm |
| Mounting hole diameter | 4.5 mm |
| Data output scaling | 24 AC current/voltage values; output 10000 corresponds to rated range |
| Frequency range (channels 13-24) | 30-100 Hz |
| Zero-point shielding | 0-50 (maximum shielding value is 0.5% of range) |
| Response time settings | 100, 80, 60, 40, 20, 400, 1000 ms |
It can measure 24 channels of AC current or voltage.
It uses an RS485 interface with the standard Modbus-RTU protocol.
The accuracy class is 0.2%.
Short INIT and G1, then power on; this is only effective in software setting mode.