User manual for the Zhongchuang Zhihe ZH-194H three-phase harmonic multifunction power meter, covering specifications, installation, wiring, and programming.
The ZH-194H from Shenzhen Zhongchuang Zhihe Technology is a three-phase harmonic multifunction power meter. It provides programmable measurement and display of three-phase voltage, current, active power, reactive power, apparent power, power factor, and frequency. It also supports harmonic measurement, power quality analysis, four-quadrant energy measurement, RS485 communication with MODBUS-RTU, and energy pulse output.
The manual describes technical specifications, installation dimensions and method, terminal wiring, and programming operations. Optional functions listed include four analog outputs, four relay outputs, four digital inputs, one external temperature measurement input, and a second RS485 interface. Programming uses the SET key and a factory-default password of 1111. This manual is written in Chinese.
| Measurement Wiring | Three-phase four-wire / three-phase three-wire |
|---|---|
| Voltage Range | AC 400 V / 100 V |
| Current Range | AC 5 A / 1 A |
| Frequency | 45–65 Hz, accuracy ±0.02 Hz |
| Measurement Accuracy | 0.5 class |
| Harmonic Measurement | Voltage and current 2nd to 31st harmonics, accuracy 1% |
| Temperature Measurement | -40 to 120 °C, accuracy ±0.5 °C |
| Communication | RS485, MODBUS-RTU, 1200–19200 bps |
| Relay Output | 4 channels, contact capacity AC250V/3A, DC30V/3A |
| Analog Output | 4 channels (DC0–20mA, DC4–20mA, DC0–5V, etc.), accuracy 0.5 class |
| Auxiliary Power | AC/DC85–265V, AC380V±5%, <5VA |
| Display | FSTN LCD or LED |
| Operating Temperature | -10 to 55 °C; storage -20 to 85 °C |
It uses an RS485 interface with the MODBUS-RTU protocol and supports baud rates from 1200 to 19200.
The factory-default user password is 1111.
It measures voltage and current harmonics from the 2nd to 31st order with 1% accuracy.
Three-phase three-wire wiring can use only two CTs on phases A and C, while three-phase four-wire wiring requires three CTs.