Watlow DIN-A-MITE Style C solid-state power controller user's manual: mounting, wiring, specifications, model ordering codes and semiconductor fuse…
This user's manual covers the Watlow DIN-A-MITE Style C solid-state power controller (document 0600-0025-0009 Rev Q, dated January 2016). The controller is available for single-phase, 3-phase 2-leg and 3-phase 3-leg operation from 120 to 600V (ac), with current switching capabilities from 30 to 80A depending on the model ordered. Zero-cross variable time base and ac/dc contactor versions are available, and phase angle or phase angle with current limit control is offered on single-phase models. Shorted SCR and open-heater alarm options are available on some zero-cross models.
The manual gives general specifications, input command signal and input control signal types, alarm behavior, agency approvals, and mounting options for DIN rail, back panel and through-wall installation, including terminal wire ranges and torque values. It also contains the DIN-A-MITE C ordering information code, a DC current rating table, output rating curves and a table of semiconductor fuses and fuse holders for applications through 600V (ac).
| Current switching capability | 30 to 80A depending on model |
|---|---|
| Maximum surge current | 1,350 A peak for 16.6 ms |
| Maximum I2t for fusing | 9100 A2s |
| Latching current | 500 mA minimum |
| Holding current | 200 mA minimum |
| Off-state leakage | 1 mA maximum at 25°C |
| Power dissipation | 1.2 W per amp switched per controlled leg |
| Storage temperature | -40 to +85°C (-40 to 185°F) |
| Input terminal wire range | 0.2 to 1.5 mm2 (24 to 16 AWG), 0.5 Nm torque |
| Line, load and ground terminal wire range | 2.5 to 25 mm2 (14 to 3 AWG), 2.7 Nm torque |
| DIN rail | DIN EN 50022, 35 by 7.5 mm |
| Weight | 1.0 to 1.9 kg (2.2 to 4.2 lb) depending on model |
The controller is made for single-phase, 3-phase 2-leg and 3-phase 3-leg operation from 120 to 600V (ac), and is also offered for 24 to 48V (ac) units.
Current switching capability ranges from 30 to 80A, depending on the model ordered.
The manual states that line and load terminals should be retorqued every 3 to 6 months, and also after 48 hours to minimize wire cold flow.
It mounts on DIN EN 50022 rail, 35 by 7.5 mm, with a clipping distance between 34.8 mm and 35.3 mm.