This manual introduces the user manual of HG series mercury displacement relay.
This user's manual covers the Watlow HG Series mercury displacement relay, including 30, 35, 50, 60, 80, 100, and 150 amp models in one-, two-, and three-pole configurations. It gives dimensions and mounting slots, wiring examples, and warnings that the relay must be mounted vertically and switches AC current only.
The manual also provides field coil power requirements and temperature control output guidance, model ordering information, return and warranty terms, and a specifications table with fusing and agency approval details. It is identified as WMDR-XUMN-1097, dated June 1997.
| Maximum load voltage | 480/600 V ac, model dependent |
|---|---|
| Load frequency | 50/60 Hz |
| Operating ambient temperature | -35 to 55°C |
| Storage temperature | -40 to 100°C |
| Contact resistance (typical) | 4 mΩ |
| Contact type | N.O. |
| Load type | Resistive |
| UL file number | ULE177629 |
| CSA file number | LR22416 |
It must be mounted vertically. Otherwise the contacts may not turn off and full voltage may be supplied to the load.
No. The contacts switch AC current only and are not for use with DC current.
Watlow recommends a Bussmann type JJN or JJS (Class T) fuse or equivalent.
It is warranted to be free of defects in material and workmanship for 18 months after delivery to the first purchaser for use, if not misapplied.