Watlow HG Series Mercury Displacement Relay User's Manual

This manual introduces the user manual of HG series mercury displacement relay.


Watlow HG Series Mercury Displacement Relay User's Manual - cover page
Brand
Watlow
Category
RELAY
Document type
User Manual
Language
English
Pages
6
File format
PDF
File size
175 KB
Published
26 October, 2023
Updated
26 October, 2023
MD5 checksum
26C8CCAC9E40CEB760363482AFD4A3C7

About this manual

This user's manual covers the Watlow HG Series mercury displacement relay, including 30, 35, 50, 60, 80, 100, and 150 amp models in one-, two-, and three-pole configurations. It gives dimensions and mounting slots, wiring examples, and warnings that the relay must be mounted vertically and switches AC current only.

The manual also provides field coil power requirements and temperature control output guidance, model ordering information, return and warranty terms, and a specifications table with fusing and agency approval details. It is identified as WMDR-XUMN-1097, dated June 1997.

What's inside

  • Dimensions
  • Wiring
  • Field Coil Power Requirements
  • Ordering Information
  • Returns
  • Warranty
  • Specifications
  • Fusing
  • Agency Approvals

Specifications

Maximum load voltage480/600 V ac, model dependent
Load frequency50/60 Hz
Operating ambient temperature-35 to 55°C
Storage temperature-40 to 100°C
Contact resistance (typical)4 mΩ
Contact typeN.O.
Load typeResistive
UL file numberULE177629
CSA file numberLR22416

Frequently asked questions

How must the HG Series relay be mounted?

It must be mounted vertically. Otherwise the contacts may not turn off and full voltage may be supplied to the load.

Can the relay switch DC current?

No. The contacts switch AC current only and are not for use with DC current.

What fuse type does Watlow recommend for the MDR load circuit?

Watlow recommends a Bussmann type JJN or JJS (Class T) fuse or equivalent.

What is the warranty period for the mercury relay?

It is warranted to be free of defects in material and workmanship for 18 months after delivery to the first purchaser for use, if not misapplied.

Download PDF (175 KB)