Manual for W&T Web-Thermograph NTC/PT100 models 57607-57615 covering installation, configuration, operation, alarms and technical data.
The W&T Web-Thermograph models 57607, 57608, 57609, 57610, 57614 and 57615 acquire, store and display temperature data and provide alarm functions that can be used in your own applications or existing systems. The manual covers installation, configuration and operation, including network connection, IP assignment, sensor connection, graph display, data logging and alarm delivery.
Depending on model, the units support NTC 10k or PT100/PT1000 sensors and 10/100BaseT Ethernet; PoE models 57614 and 57615 can be powered over Ethernet. Technical data, firmware update, emergency access and disposal instructions are included in the appendix.
| Network | 10/100BaseT autosensing |
|---|---|
| Supply voltage | 12-24 V AC/DC via screw terminals; PoE or 18-48 V DC / 18-30 V AC via screw terminals |
| NTC sensor measuring range (57609, 57614) | -45 C to 75 C |
| PT100/PT1000 measuring input (57607, 57608, 57610, 57615) | -200 C to 650 C |
| W&T sensor measuring range (57607, 57608, 57610, 57615) | -50 C to 180 C |
| Measuring error (NTC model) | +/-0.3 C, +/-5% |
| Storage frequency | 1, 5, 15, 60 min |
| Memory depth | min. 14 weeks, max. 16 years (57609/57610/57614/57615); min. 4 weeks, max. 4 or 8 years (57607/57608) |
| Housing | 105 x 75 x 22 mm (57609/57610/57614/57615); 106.8 x 87.8 x 62.6 mm (57607/57608) |
| Ambient operating temperature | 0 to +60 C |
| Ambient storage temperature | -40 to +70 C |
| Weight | approx. 200 g (57607/57608) |
Models 57609 and 57610 use 12-24 V AC/DC via screw terminals, while PoE models 57614 and 57615 can use Power-over-Ethernet or an external 18-48 V DC or 18-30 V AC supply.
Model 57609/57614 use an NTC 10k sensor, and models 57607/57608/57610/57615 support PT100/PT1000 sensors with 2-, 3- or 4-conductor connections.
Using emergency access over the serial terminal, press the letter f three times within the first three seconds after power-on.
After disconnecting cables and sensors, open the housing, remove the button battery from the circuit board, and take it to an official recycling collection site.