This document is a Web-Thermograph product manual that introduces the connection, configuration and use methods of the product
The W&T Web-Thermograph combines temperature acquisition, storage and display in one box, with numerous alarm functions that can be incorporated into your own applications or existing systems. This manual contains the information needed to install, configure and operate the device.
The document starts with quick start and start-up: connecting the power supply for models 57609/57610 and 57607/57608, the PoE power supply for 57614/57615, connecting NTC, PT100 and PT1000 sensors, the Ethernet connection and IP address assignment with WuTility or DHCP. Later sections cover online measurement storage in the W&T Cloud, the graph display of measurements, port and device names, time setting, data logger configuration, calibration, e-mail/SNMP/TCP/FTP/Syslog alarms, ASCII command strings, single polling of temperatures via TCP/IP, UDP and SNMP, embedding values in your own web site, the data logger, firmware update, emergency access and technical data.
| Network | 10/100BaseT autosensing |
|---|---|
| Supply voltage | 12-24V AC/DC with screw terminals |
| PoE supply voltage | Power-Over-Ethernet or 18-48V DC or 18-30V AC via screw terminals |
| Sensor (57609, 57614) | NTC 10k |
| Measuring range (NTC models) | -45°C...75°C |
| Sensor (57610, 57615) | Pt100, Pt1000 connection, 2-, 3- or 4-conductor |
| PT100/PT1000 measuring input | -200°C...650°C |
| Resolution | 1/10°C |
| Storage frequency | 1, 5, 15, 60 min |
| Housing | Compact plastic housing, 105 x 75 x 22mm (l x w x h) |
| Configuration interface | serial port RS232, 9600 baud, 8 data bits, 1 stopbit, no parity |
| Ambient operating temperature | 0..+60°C |
Connect the supply voltage of 12-24V AC/DC to the terminal provided using the AC adapter provided; polarity does not need to be observed.
Models 57614 and 57615 are the PoE versions, designed for use in PoE environments in accordance with IEEE802.3af.
Using the serial emergency access, press the letter "f" three times in the first three seconds after powering on; all configuration settings including the IP address are lost.
A non-rechargeable lithium button battery type BR (lithium carbon monofluoride) retains the time when the device is turned off.