Installation manual for Victron Energy VDI-16, VDI-32 and VDI-64 galvanic isolators: mounting, ventilation, grounding wiring and specifications.
The Victron Energy VDI-16, VDI-32 and VDI-64 are waterproof (potted) galvanic isolators for vessel grounding systems. The installation manual gives mounting location requirements and wiring instructions, including a wiring diagram; the text is provided in several languages.
The manual instructs that the product be installed in a heat-resistant, well-ventilated area with 10 cm of clear space and mounted lengthwise vertical for cooling. It must be wired into the green (safety) grounding connection ahead of all vessel grounding connections. The specification table lists current ratings, peak current, M6 connection, anodized aluminium heat sink, IP 67 protection, weight and dimensions.
| Maximum current | VDI-16: 16 A; VDI-32: 32 A; VDI-64: 64 A |
|---|---|
| Peak current (20 ms) | VDI-16: 1600 A; VDI-32: 3200 A; VDI-64: 6000 A |
| Connection | M6 |
| Heat sink material | Anodized aluminium |
| Protection category | IP 67 |
| Weight | VDI-16: 1 kg; VDI-32: 2 kg; VDI-64: 3.2 kg |
| Dimensions (hxwxd), VDI-16 | 60 x 120 x 200 mm |
| Dimensions (hxwxd), VDI-32 | 63 x 164 x 200 mm |
| Dimensions (hxwxd), VDI-64 | 63 x 164 x 335 mm |
It should be installed in a well-ventilated area.
Keep 10 cm of clear space around the product.
It must be mounted with its length vertical to allow maximum cooling.
It is wired into the green (safety) grounding connection as shown in fig. 1.