Installation and operation manual for the Sponsler SP712-2 loop powered 4-20mA transmitter, covering specifications, bench calibration and loop wiring.
This is the installation and operation manual (DOC# MN-712-C, Rev. C) for the Sponsler SP712-2, a 2-wire loop powered analog transmitter that linearly converts a frequency input to an equivalent 4-20mA current output. Used with a turbine flowmeter, it provides a current representation proportional to flow, and current-format data transmission gives noise immunity and long distance transmission capability. A full-scale frequency range of 100 Hz - 10 KHz is selectable via switch S1.
The manual lists the transmitter specifications, including operating and storage temperatures, input voltage limits, signal input, analog output, response time, linearity, tempco, enclosure ratings and weight. It then gives a bench test calibration procedure using a power supply, digital multimeter, frequency generator and frequency counter, with zero (R25) and span (R19) adjustments, sensitivity adjustment (R1) and a linearity check formula, followed by typical loop configurations, a terminal location and outline drawing, and the note that lamp D1 illuminates while test button S2 is depressed if both signal and power are present.
| Operating temperature | -40 to 85 °C |
|---|---|
| Storage temperature | -65 to 125 °C |
| Minimum input voltage | 7 V + (20mA x RL) |
| Maximum input voltage | 28 V + (4mA x RL) |
| Signal input frequency | 0 - 10 KHz |
| Signal input amplitude | 50 mV - 35 V sine or square wave |
| Input impedance | 50K |
| Analog output | 4mA @ 0 Hz, 20mA @ desired full scale frequency |
| Full scale frequency range | 100 Hz - 10 KHz selectable via S1 |
| Response time | 95% of change in 1 second |
| Linearity | 0.3% F/S |
| Tempco | < 2% of reading over entire temperature range |
| Enclosure | FM Approved, CSA Certified Class I Groups B, C, D; Class II Groups E, F, G |
| Weight | 1.7 lbs |
Only two wires, because it is a true 2-wire transmitter: input power and signal output use the same wires.
A full scale frequency range of 100 Hz to 10 KHz is selectable via switch S1.
Use the formula (F/F max X 16) + 4 = mA, where F is the flowrate frequency in Hz and Fmax is the frequency at which 20mA is set.
When S2 is depressed, lamp D1 illuminates if loop voltage and input signal are both present.