Sola/Hevi-Duty CVS Series Constant Voltage Transformer Operating and Service Manual

Sola/Hevi-Duty CVS Series Constant Voltage Transformer Operating and Service Manual covering installation, mounting, electrical connections, and operation…


Sola/Hevi-Duty CVS Series Constant Voltage Transformer Operating and Service Manual - cover page
Brand
Sola Hevi Duty
Category
transformer
Document type
Service Manual
Language
English
Pages
2
File format
PDF
File size
2.1 MB
Published
21 November, 2026
Updated
21 November, 2026
MD5 checksum
00153E30698E074559E40152875151E3

About this manual

This operating and service manual covers Sola/Hevi-Duty Constant Voltage Sinusoidal (CVS) Transformers. It helps users operate and service the CVS transformer with minimal effort.

The manual provides mechanical mounting instructions, electrical connection diagrams, recommended wire sizes and fusing, and guidance for operation with rectifier, motor, cascade, three-phase, and switchmode power supply loads.

What's inside

  • Introduction
  • Installation - Mechanical Position
  • Mounting Considerations
  • Installation - Electrical
  • Multiple Operation
  • Use With Rectifier Loads
  • Operation With Motor Loads
  • Cascade Operation
  • Three-Phase Power Wiring
  • Use With Switchmode Power Supplies

Specifications

Mounting OrientationThis side up
Cooling MethodNatural draft air circulation
Output IsolationIsolated from input lines
Crest to RMS RatioApproximately 1.3 at rated load
RegulationStandard ±1%
Supply Line VariationUp to ±15%
Cascade Output VariationUp to 0.25%

Frequently asked questions

How should CVS transformers with end housings be mounted?

Mount them with the silk-screened “this side up” legend facing upward so the ventilated capacitor compartment faces downward.

Can two CVS transformers be connected in parallel?

Yes, two CVS transformers with the same rating may be connected with their inputs and outputs in parallel, though standard ±1% regulation cannot be guaranteed.

Are CVS transformer outputs isolated from the input lines?

Yes, the outputs of all standard CVS transformers are isolated from the input lines.