Sola/Hevi-Duty CVS Series Constant Voltage Transformer Operating and Service Manual covering installation, mounting, electrical connections, and operation…
This operating and service manual covers Sola/Hevi-Duty Constant Voltage Sinusoidal (CVS) Transformers. It helps users operate and service the CVS transformer with minimal effort.
The manual provides mechanical mounting instructions, electrical connection diagrams, recommended wire sizes and fusing, and guidance for operation with rectifier, motor, cascade, three-phase, and switchmode power supply loads.
| Mounting Orientation | This side up |
|---|---|
| Cooling Method | Natural draft air circulation |
| Output Isolation | Isolated from input lines |
| Crest to RMS Ratio | Approximately 1.3 at rated load |
| Regulation | Standard ±1% |
| Supply Line Variation | Up to ±15% |
| Cascade Output Variation | Up to 0.25% |
Mount them with the silk-screened “this side up” legend facing upward so the ventilated capacitor compartment faces downward.
Yes, two CVS transformers with the same rating may be connected with their inputs and outputs in parallel, though standard ±1% regulation cannot be guaranteed.
Yes, the outputs of all standard CVS transformers are isolated from the input lines.