This manual covers Sola/Hevi-Duty Constant Voltage Sinusoidal (CVS) Transformers installation, maintenance and operation.
This operating and service manual is designed to ensure the Sola/Hevi-Duty Constant Voltage Sinusoidal (CVS) Transformers can be operated and serviced with minimal effort. It covers mechanical positioning requirements, such as mounting units with the silk-screened legend facing upwards for cooler capacitor operation, though satisfactory performance is achieved in any horizontal position.
| Frequency | 60 Hz |
|---|---|
| Regulation Accuracy | Standard ±1% |
Yes, two CVS transformers with the same rating may be connected with their inputs and outputs in parallel.
Units should be mounted with the silk-screened legend facing upwards to place the ventilated capacitor compartment downward.
The transformer must have a load rating nearly equal to the maximum power drawn during the starting cycle, which may run from two to eight times the normal running rating.