Sloan TruFlush Electronic Flushometer Installation Guide

Installation instructions for Sloan TruFlush electronic flushometers, including tools, sensor operation, battery replacement, and troubleshooting.


Sloan TruFlush Electronic Flushometer Installation Guide - cover page
Brand
Sloan
Document type
Installation Guide
Language
English
Pages
11
File format
PDF
File size
5.8 MB
Published
04 November, 2026
Updated
04 November, 2026
MD5 checksum
1B1DBBFC4ADB4BE2279BB79E18BD3372

About this manual

This guide provides step-by-step instructions for installing Sloan TruFlush electronic flushometers in closets and urinals. It covers required tools, wall bracket installation, sensor and battery assembly, water flow adjustment, and sensor operation testing. The document also includes warranty details and important safety notes for proper installation and operation.

The TruFlush models listed are TRF 8156-1.6, TRF 8156-1.28, TRF 8156-1.1, TRF 8196-0.5, TRF 8196-0.25, and TRF 8196-0.125. The valve requires a minimum 6-inch wall space depth and a 5.6” x 5.6” wall plate opening. Installation must be done with proper plumbing connections and without using pipe sealant or plumbing grease on valve components.

What's inside

  • Tools Required for Installation
  • Wall Bracket Installation
  • Battery Box and Sensor Assembly
  • Sensor Operation
  • Water Flow Adjustment
  • Wall Plate Installation
  • Warranty Information
  • Important Installation Notes

Frequently asked questions

What is the minimum wall space depth required for installing this flushometer?

This valve is designed for minimum six inch (152 mm) wall space depth.

What is the required water pressure range for the flushometer to operate?

Sloan’s flushometers are designed to operate with 20 to 80 PSI (138 to 552 KPA) of water pressure.

What is the sensor’s factory-set sensing range for water closet models?

The factory setting for water closet models is 22” to 46” (559 mm to 1168 mm).

What is the required transformer output voltage for hardwired operation?

The output voltage of the transformer must be 6VAC for the unit to function properly.