A repair parts and maintenance guide for the Sloan Optima Plus Flushometer, covering parts lists, installation, troubleshooting, and battery replacement.
This document serves as a comprehensive repair parts and maintenance guide for the Sloan Optima Plus Flushometer. It provides detailed parts lists with code numbers and descriptions, along with specific instructions for installing components like the Flex Tube Diaphragm Assembly and Vacuum Breakers. The guide also includes a troubleshooting section to help diagnose common issues such as sensor range problems, flushing failures, and water volume discrepancies.
| Sensing Range (Water Closet) | 22 to 42 inches (559 mm to 1067 mm) |
|---|---|
| Sensing Range (Urinal) | 15 to 30 inches (381 mm to 762 mm) |
| Battery Type | four (4) Alkaline AA-Size Batteries |
| Flush Volume (Urinal) | 0.5 gpf/1.9 Lpf to 1.0 gpf/3.8 Lpf |
| Flush Volume (Closet) | 1.6 gpf/6.0 Lpf to 2.4 gpf/9.0 Lpf |
Loosen the two screws on top of the unit, remove the Cover Assembly, lift the Sensor Module, and replace the four Alkaline AA-Size Batteries.
Push the manual override button for 20-30 seconds until the Red LED blinks, release the button, and wait for the setting mode to run for one minute.
Use only soap and water, then wipe dry with a clean cloth or towel. Do not use abrasive or chemical cleaners.