Siemens SITRANS FUS1010 Flow Measurement Display Transmitter

Clamp-on ultrasonic flow transmitter with transit time and Doppler modes for liquids with suspended solids or aeration.


Siemens SITRANS FUS1010 Flow Measurement Display Transmitter - cover page
Brand
Siemens
Document type
User Manual
Language
English
Pages
9
File format
PDF
File size
524 KB
Published
23 November, 2026
Updated
23 November, 2026
MD5 checksum
0CA25F1989A1BC1E4F6B78E3AF83A427

About this manual

The SITRANS FUS1010 is a versatile clamp-on ultrasonic flow display transmitter that operates in either wide-beam transit time or reflexor (Doppler) mode. It is suitable for various liquids, including those with high aeration or suspended solids. Available in single, dual, or optional four-channel configurations, it supports IP65 (NEMA 4X) and IP66 (NEMA 7) enclosures. Features include easy installation, minimal maintenance, no pressure loss, and wide turndown ratio.

Applications span water, wastewater, HVAC, power, and processing industries. It offers bidirectional flow operation, 1 MByte data logger, and multiple communication options including HART, BACnet, Modbus, and Ethernet IP. Language options include English, Spanish, German, Italian, and French.

What's inside

  • Overview
  • Benefits
  • Application
  • Design
  • Function
  • Technical Specifications
  • Selection and Ordering

Specifications

Flow Range±12 m/s (±40 ft/s), bidirectional
Flow Sensitivity0.0003 m/s (0.001 ft/s), flow rate independent
Pipe Size6.4 mm ... 9.14 m (0.25“ ... 360“)
Accuracy±0.5% ... 1.0% of flow for velocities > 0.3 m/s (1 ft/s)
Data Refresh Rate5 Hz
Display128 x 240 pixel LCD with back-light
Keypad33 keypad buttons with tactile feedback
Language OptionsEnglish, Spanish, German, Italian, French
Power Supply90 ... 240 V AC, 50 ... 60 Hz, 30 VA or 9 ... 36 V DC, 12 W
Data Logger Memory1 MByte

Frequently asked questions

What flow measurement modes does the SITRANS FUS1010 support?

It supports wide-beam transit time and reflexor (Doppler) modes.

What communication options are available?

It supports HART, BACnet MSTP/BACnet IP, Modbus RTU & TCP/IP, Ethernet IP, Johnson N2, and VT100 RS 232.

What are the language options for the display?

Languages include English, Spanish, German, Italian, and French.