Siemens SITRANS F M MAG 5000/6000 Electromagnetic Flowmeter Operating Instructions

Operating instructions for Siemens SITRANS F M MAG 5000/6000 electromagnetic flow transmitters, covering installation, commissioning, maintenance, functions…


Siemens SITRANS F M MAG 5000/6000 Electromagnetic Flowmeter Operating Instructions - cover page
Brand
Siemens
Category
Other products
Document type
User Manual
Language
English
Pages
98
File format
PDF
File size
11.2 MB
Published
21 November, 2026
Updated
21 November, 2026
MD5 checksum
2AE636C57C2575777655A35357DDD4AC

About this manual

This document is the operating instructions for Siemens SITRANS F M MAG 5000/6000 electromagnetic flow transmitters for compact and remote installation. It covers safety notes, description, installation and mounting, electrical connection, commissioning, service and maintenance, functions, alarm and error messages, troubleshooting, technical data, spare parts and accessories, and menu diagrams.

Versions described include standard transmitters and optional Blind, CT and SV versions. Technical data include measuring principle, input and output characteristics, ambient temperature ranges, degree of protection, power supply and consumption, and certificates and approvals.

What's inside

  • Introduction
  • Safety notes
  • Description
  • Installing/Mounting
  • Connecting
  • Commissioning
  • Service and maintenance
  • Functions
  • Technical data
  • Menu diagrams

Specifications

Measuring principleElectromagnetic with pulsed constant field
Empty pipe detectionDetection of empty pipe (special cable required in remote mounted installation)
Electrode input impedance> 1 x 10^14 Ω
Current output0 ... 20 mA or 4 ... 20 mA, load < 800 Ω
Digital output frequency0 ... 10 kHz, 50% duty cycle
Relay output load42 V AC/2 A, 24 V DC/1 A
Low flow cut off0 ... 9.9% of maximum flow
Galvanic isolationAll inputs and outputs are galvanically isolated
Maximum measuring errorMAG 5000: 0.4% ± 1 mm/s; MAG 6000: 0.2% ± 1 mm/s (v > 0.1 m/s)
Ambient temperature (operation)Standard IP67, 19", blind and SV versions: -20 ... +60 °C; CT version: -20 ... +50 °C
Degree of protectionIP67/NEMA 4X/6
Power supply115 ... 230 V AC +10% -15%, 50 ... 60 Hz; or 11 ... 30 V DC / 11 ... 24 V AC
Weight0.75 kg (2 lb)
Certificates and approvalsCE, C-UL US general purpose, C-tick, CSA/FM Class 1, div 2

Frequently asked questions

What is the degree of protection?

The degree of protection is IP67/NEMA 4X/6 to IEC 529 and DIN 40050 (1 mH2O 30 min.).

What power supply options are listed?

The listed power supply options are 115 ... 230 V AC +10% -15%, 50 ... 60 Hz, or 11 ... 30 V DC / 11 ... 24 V AC.

What is the maximum measuring error?

The maximum measuring error is 0.4% ± 1 mm/s for MAG 5000 and 0.2% ± 1 mm/s for MAG 6000 for v > 0.1 m/s.

What approvals are listed?

The listed approvals include CE, C-UL US general purpose, C-tick, CSA/FM Class 1, div 2, plus custody transfer approvals for CT versions.