Siemens SIMATIC S7-1500 Type Test Certificate

Siemens SIMATIC S7-1500 type test certificate, version 03/2016 No. 106, listing applied IEC/EN standards and environmental and EMC tests.


Siemens SIMATIC S7-1500 Type Test Certificate - cover page
Brand
Siemens
Category
Automation control Equipment
Document type
Other
Language
German
Pages
14
File format
PDF
File size
1.2 MB
Published
11 November, 2026
Updated
11 November, 2026
MD5 checksum
1B39662FE51DE43355AA5E6F9FD93EC1

About this manual

This is a Siemens SIMATIC S7-1500 type test certificate, version 03/2016, No. 106, issued in Amberg on 21 March 2016. It states that the requirements of the applied test specifications are met.

The certificate lists power supply, central processing unit, interface, digital input/output, analog, communication processor and function modules that comply when the installation guidelines are followed, along with accessories. The test sections cover temperature change, cold, dry heat, damp heat, gas exposure, vibration, shock and burst. This manual is written in German.

What's inside

  • Applied standards
  • Modules covered
  • General information and approvals
  • Temperature change tests
  • Cold tests
  • Dry heat test
  • Damp heat test
  • Gas tests
  • Vibration tests
  • Shock tests

Specifications

Applied standardsIEC 60068-x / EN 60068-x; IEC 61000-4-x / EN 61000-4-x
Temperature change test, operation0 °C to +60 °C; 3 h; 3 K/min; 5 cycles
Dry heat test, storage+70 °C; 16 h
Damp heat test, storage+25 °C to +55 °C; 95% relative humidity; 48 h
Shock test, operation150 m/s²; 11 ms; 3 shocks per axis
Burst test2 kV for power supplies and signal lines

Frequently asked questions

Which standards are listed for the SIMATIC S7-1500 type test?

The certificate lists IEC 60068-x / EN 60068-x and IEC 61000-4-x / EN 61000-4-x among the applied standards.

What does the certificate say about the test result?

It states that the requirements of the applied test specifications are met.

Are the devices and modules approved by cULus or FM?

The general information says the devices and modules are e.g. approved by cULus, cULus Hazardous Location, or FM. The assigned approval is shown on the identification label or packaging, excluding accessories.

What temperature change test is listed for operation?

It lists 0 °C to +60 °C, 3 h exposure, 3 K/min change speed, and 5 cycles.