Siemens QAC22 outdoor sensor technical instructions: measuring range, LG-Ni 1000 sensing element, accuracy, wiring, mounting location and dimensions.
These technical instructions from Siemens Building Technologies describe the QAC22 outdoor sensor, which measures the outside temperature and, to a lesser degree, the effect of solar radiation and wind and the temperature of the wall. It is used as a reference sensor for weather-dependent flow temperature control, or as a measuring sensor for optimization functions, value display or connection to a building management system. The sensor has a plastic casing with a removable cover, interchangeable terminals and cable entry from the rear or from below, with an optional PG11 cable entry gland.
The document lists specifications such as the –58°F to 158°F (–50°C to 70°C) measuring range, the LG-Ni 1000 Ω thin film sensing element, accuracy of ±0.4K at 32°F (0°C) and a time constant of approximately 14 minutes. It also gives engineering notes on cable length, installation guidance on mounting location and height, resistance and accuracy characteristic diagrams, and dimensions in inches and millimeters.
| Measuring range | –58°F to 158°F (–50°C to 70°C) |
|---|---|
| Sensing element | LG-Ni 1000 Ω thin film element |
| Accuracy | ±0.4K @ 32°F (0°C) |
| Time constant | Approximately 14 minutes |
| Storage/transportation temperature | –13°F to 149°F (–25°C to 65°C) |
| Storage/transportation humidity | <85% rh |
| Operating humidity | 0 to 100% rh |
| Electrical connections | Interchangeable terminals; cable entry gland PG11 can be fitted |
| Weight | 0.2 lb. (0.76 kg) |
| Color | White |
The measuring range is –58°F to 158°F (–50°C to 70°C).
It uses an LG-Ni 1000 Ω thin film element whose resistance changes as a function of the temperature.
Do not expose it to the morning sun; if in doubt, mount it on the north or northwest wall, at least 8 feet (2.5 m) above the ground.
No. Do not paint over the sensor.