Siemens SINAMICS G150HP Installation Checklist

Installation checklist for the Siemens SINAMICS G150HP cabinet device, covering mechanical and electrical installation steps.


Siemens SINAMICS G150HP Installation Checklist - cover page
Brand
Siemens
Category
inverter
Document type
Installation Guide
Language
German
Pages
32
File format
PDF
File size
667 KB
Published
11 November, 2026
Updated
11 November, 2026
MD5 checksum
1D7CC85E2E45C3B8A0153BA8C9E894D7

About this manual

This document is a checklist for the mechanical and electrical installation of the Siemens SINAMICS G150HP cabinet device. It is an excerpt from the operating manual and lists installation steps to be checked off.

It covers power and signal connections, transport-unit connections, EMC shielding, fan transformer voltage adaptation, and optional equipment such as du/dt filters, external auxiliaries, cabinet lighting, standstill heating, auxiliary power supply, customer terminal strip, and SMC30 sensor modules. This manual is written in German.

What's inside

  • Mechanical installation checklist
  • Electrical installation checklist
  • Power connections
  • Signal connections
  • Option L07 du/dt filter compact plus Voltage Peak Limiter
  • Option L10 du/dt filter plus Voltage Peak Limiter
  • Option L19 connection for external auxiliary drives
  • Option L21 overvoltage limitation
  • Option L50 cabinet lighting with service socket
  • Option L55 standstill heater

Specifications

Power cable tightening torque50 Nm
External auxiliary drive load currentmax. 10 A
Cabinet lighting supply protectionmax. 10 A
Standstill heater supply230 V / 50 Hz, 100 W (or 2 x 100 W for 800-1200 mm cabinets)
Standstill heater supply protectionmax. 16 A
Default SMC30 encoder settingHTL encoder, bipolar, 1024 pulses per revolution

Frequently asked questions

What torque must be used when connecting power cables to the cabinet?

The power cables must be connected with a torque of 50 Nm.

When must the DC link capacitors be formed?

Forming is required if the cabinet has been stationary for more than 2 years.

What is the maximum load current for external auxiliary drives on option L19?

The load current may be a maximum of 10 A.

What is the default encoder setting of the SMC30 sensor module?

In the delivery state, an HTL encoder is set bipolar with 1024 pulses per revolution.