Siemens FAQ on macro 51 Modbus RTU control for the G120XA inverter: macro selection, setting steps, terminal definitions and parameters.
This Siemens FAQ document explains preset interface macro 51 (Modbus RTU control) for the G120XA inverter. It describes how preset macros configure most of the inverter terminals, how to select a macro during quick commissioning with parameter p0015, and the three steps needed to activate macro 51.
The document then gives the function description and terminal definition for macro 51: start/stop via digital input DI0 and speed adjustment over the Modbus RTU bus. Two parameter tables follow, one listing the parameters the inverter sets automatically and one listing the parameters that must be set manually, such as baud rate, fieldbus address, parity and fieldbus monitoring time. This manual is written in Chinese.
| P2030 fieldbus protocol | 2 (Modbus RTU) |
|---|---|
| P2020 RS485 baud rate | 8 |
| P2021 RS485 fieldbus address | 0 |
| P2031 Modbus RTU parity | 2 (even parity) |
| P2040 fieldbus monitoring time | 1000 ms |
Set P0010=1, change P0015=51 to select Modbus RTU control, then set P0010=0.
No. P0015 can only be changed when P0010=1.
Start/stop is controlled by digital input DI0; when the DI0 signal is opened the motor coasts to a standstill.
The speed is controlled over the Modbus RTU bus; the register addresses are given in chapter 6.2.3 of the G120XA operating manual.