Siemens ET 200SP HA DQ 32x24VDC/0.5A HA Digital Output Module Device Manual

This manual covers the safety, installation, wiring, parameterization, and technical specifications for the Siemens ET 200SP HA DQ 32x24VDC/0.5A HA digital…


Siemens ET 200SP HA DQ 32x24VDC/0.5A HA Digital Output Module Device Manual - cover page
Brand
Siemens
Category
Industrial Robot
Document type
User Manual
Language
Chinese
Pages
42
File format
PDF
File size
397 KB
Published
21 October, 2026
Updated
21 October, 2026
MD5 checksum
DF3A8A7DE7263DB4258F7B29A0DE26E1

About this manual

This document is the device manual for the Siemens ET 200SP HA digital output module, model DQ 32x24VDC/0.5A HA (part number 6DL1132-6BL00-0PH1). It provides essential information for the safe operation, installation, and configuration of the module within distributed I/O systems.

The manual details the module's physical attributes, including its 32 digital output channels and source-type (PNP) configuration. It covers critical topics such as safety warnings, wiring diagrams for single and two-wire connectors, parameter settings, status display indicators, and technical data. Additionally, it explains the use of the output disable switch for safe removal during operation and provides information on drivers and address spaces for use outside the PCS 7 environment. This manual is written in Chinese.

What's inside

  • Safety Information
  • Product Overview
  • Wiring
  • Parameters
  • Display and Interrupts
  • Technical Data
  • Drivers and Address Space
  • Output Disable Switch
  • Module Attributes
  • Index

Specifications

Number of Digital Outputs32
Output Voltage24VDC
Output Current (Single Channel)0.5 A
Output Current (Total)10 A
Output TypeSource-type (PNP)
Part Number6DL1132-6BL00-0PH1

Frequently asked questions

How do you safely remove the I/O module while the system is running?

Press the output disable switch for 3 seconds to power off the module before removing it.

What indicates that the process value is valid?

The value status is set to 1, indicating the process value is normal or 'good'.

What happens if the module power supply voltage L+ is lost?

The module supports configurable diagnostics for the loss of the module-specific power supply voltage L+.