About this manual

Siemens SIMATIC ET 200S 2AI I 2/4WIRE HF (6ES7134-4MB02-0AB0) is an analog electronic module with two inputs for current measurement. This product manual covers its features, parameters, diagnostics, analog value representation, and connection.

Supported input ranges are ±20 mA with 15-bit plus sign resolution and 4 to 20 mA with 15-bit resolution. The module supports 2- or 4-wire transducers, clock-synchronous operation, I&M functions, and an extended temperature range of 0 to 50 °C with vertical installation. This manual is written in Italian.

What's inside

  • Features
  • Parameters
  • Diagnostics
  • Analog value representation
  • Connection
  • Pin assignment
  • Terminal modules
  • Technical data

Specifications

Number of inputs2
Input range±20 mA, 15-bit + sign resolution
Input range4 to 20 mA, 15-bit resolution
Common-mode voltageAC 100 V between channels
Transducer connection2- or 4-wire transducers
Clock-synchronous operationSupported
Clock-synchronous DP cycle time0.7 ms minimum
Clock-synchronous conversion time0.5 ms minimum
I&M functionsSupported
Temperature range0 to 50 °C with vertical installation
Width15 mm
Weightapproximately 45 g
Shielded conductor lengthmax. 200 m
Parameter length12 byte
Address area4 byte
Analog value representationS5 and S7 format
Nominal load voltage L+DC 24 V
Reverse polarity protectionyes
Transducer supply voltageyes
Short-circuit protection60 mA (both channels)
Potential separationfrom load voltage L+

Frequently asked questions

How many inputs does the module have?

It has two inputs for current measurement.

Does the module support 2- or 4-wire transducers?

Yes, it supports transducers with 2 or 4 wires.

What is the maximum shielded conductor length?

The maximum shielded conductor length is 200 m.

What is the nominal load voltage L+?

The nominal load voltage L+ is DC 24 V.