Quick start guide for installing, starting up and programming the Rockwell Automation PowerFlex 40 Adjustable Frequency AC Drive.
This quick start guide summarizes the basic steps needed to install, start up and program the PowerFlex 40 Adjustable Frequency AC Drive, FRN 1.xx - 4.xx. It does not replace the PowerFlex 40 User Manual and is intended for qualified drive service personnel only.
The guide covers general precautions, mounting considerations, minimum clearances, ambient operating temperatures, disconnecting MOVs, CE conformity, drive ratings, input/output ratings, power terminal blocks and power wiring. It includes attention notes about high voltage capacitors, ESD-sensitive parts and correct application and installation.
| Output Frequency | 0-400 Hz (Programmable) |
|---|---|
| Efficiency | 97.5% (Typical) |
| Digital Control Inputs | Input Current = 6mA |
| 4-20mA Analog Input Impedance | 250 ohm |
| Motor Protection | I2t overload protection, 150% for 60 Secs and 200% for 3 Secs |
| Control Ride Through | Minimum 0.5 Secs, typical 2 Secs |
Isolate the mains supply from the line inputs and wait three minutes for the capacitors to discharge to safe voltage levels.
The output frequency range is 0-400 Hz and is programmable.
The recommended fuse type is UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
Turn the screw counterclockwise to loosen it, pull the jumper completely out of the drive chassis, then tighten the screw.