The RDX2LE-100 leakage circuit breaker manual provides specifications, installation conditions, wiring diagrams, and protection functions.
About this manual
This manual describes the purpose, application range, and protection features of the RDX2LE-100 leakage circuit breaker, which is designed for 230 V/400 V AC systems with rated currents up to 100 A. It outlines the high breaking capacity, compact size, light weight, and convenient rail‑mount installation.
The document includes operating and installation requirements such as ambient temperature, altitude limits, humidity, and mounting guidelines, as well as detailed technical specifications, internal structure, operating principle, and wiring diagrams for proper connection and safety. This manual is written in Chinese.
What's inside
- Purpose and Application
- Operating and Installation Conditions
- Technical Specifications
- Structure and Operating Principle
- Wiring Diagram
Specifications
| Rated residual current (non‑trip) | 15 mA |
|---|
| Rated residual current (trip) | 30 mA |
|---|
| Rated residual making and breaking capacity | 2500 A |
|---|
| Residual‑current action time | ≤0.1 s |
Frequently asked questions
What ambient temperature range is allowed for operation?
The surrounding air temperature may be from –5 °C to +40 °C, and the 24 h average must not exceed +35 °C.
What is the maximum installation altitude?
Installation is permitted up to an altitude of 2000 m.
What is the rated residual current that does not cause a trip?
The rated residual non‑trip current is 15 mA.
What is the rated residual current that triggers a trip?
The standard rated residual trip current is 30 mA, but other values can be customized on request.