Rain Bird IC System Operation and Fault Diagnosis Guide

This guide provides operational instructions and troubleshooting steps for the Rain Bird IC irrigation system, including software diagnostics and field…


Rain Bird IC System Operation and Fault Diagnosis Guide - cover page
Brand
RAINBIRD
Document type
Service Manual
Language
Chinese
Pages
28
File format
PDF
File size
9 MB
Published
26 October, 2026
Updated
26 October, 2026
MD5 checksum
F2333677DA67FDA78747B75F9DFA39E0

About this manual

This document serves as a fault diagnosis and operation guide for the Rain Bird IC (Integrated Control) irrigation system. It details the use of central control software platforms such as Cirrus, Nimbus II, Stratus II, Stratus LT, and GO to identify issues within the field.

The manual covers specific diagnostic procedures for key components including the ICI (Integrated Control Interface), ICM (Integrated Control Module), and ICSD (Integrated Control Surge Device). It provides step-by-step instructions on verifying system status, checking power levels, locating communication faults, and identifying grounding issues using both software tools and physical field measurements. This manual is written in Chinese.

What's inside

  • IC System Fault Troubleshooting
  • Central Control Software Usage
  • ICI Diagnostics
  • ICM Diagnostics
  • Individual Station Status
  • Field Diagnosis Procedures
  • System Power Verification
  • Grounding Faults

Specifications

Output Voltage Range25 to 28 VAC
Minimum Threshold Voltage for Sprinkers20 V
Maximum ICMs per Line750
ICSD Replacement Current Limit2 mA

Frequently asked questions

What software platforms are used to operate the Rain Bird IC system?

The central irrigation control software platforms include Cirrus, Nimbus II, Stratus II, Stratus LT, and GO.

What is the minimum voltage required to open a sprinkler or valve?

The minimum threshold voltage required to open a sprinkler or valve is 20 V.

How many ICMs can be managed on a single line?

The central control software can manage up to 750 ICMs on a single line.

When should an ICSD be replaced?

An ICSD should be replaced if its current consumption exceeds 2 mA.