Power-Genex IPC is a two-wire I/P converter that converts a 4-20mA input into proportional output pressure.
Power-Genex IPC is an advanced two-wire I/P converter that uses piezoelectric air switching technology to produce an output pressure directly proportional to a 4-20mA input signal. The manual lists its features, specifications, ordering information, and installation steps.
The converter is intended for back-of-board installation with IP55 protection and snap-on mounting on 35 mm top hat rails. It includes built-in pressure regulation, low air consumption, and factory-set zero and span adjustments.
| Input signal | 4~20mA @ 24 VDC, 2-wire |
|---|---|
| Minimum operating voltage | 9 VDC |
| Output pressure | 0...1.0bar (0...15psi); 0.2...1.0bar (3...15psi); 0.4...2.0bar (6...30psi); 0.2...3.0bar (3...45psi) |
| Output characteristics | Linear to input signal |
| Action | Direct |
| Total error | Max. error +/-0.3% of span (linearity + hysteresis + repeatability) |
| Air supply | Oil free, dry air, filter to 5 micron; 1.5 to 3.5bar |
| Air consumption | 20 LPM |
| Pneumatic connection | 1/8" PT female |
| Protection class | IP55 |
| Impedance | 425 ohms at 20mA |
| Mounting | Rail (according to DIN EN 50022) |
| Electrical connection | PG 9 |
| Body and cover material | Aluminum diecast |
| Weight | 820 g |
It accepts a 4~20mA input signal at 24 VDC in a 2-wire configuration.
The maximum error is +/-0.3% of span, including linearity, hysteresis, and repeatability.
It is designed for snap-on mounting on 35 mm top hat rails according to DIN EN 50022.
No, the output pressure is precisely set at the factory and should not be reset by turning those screws.