Installation and maintenance manual for Power Genex PPL/EPL pneumatic and electropneumatic positioners, covering technical data, mounting and troubleshooting.
Power Genex PPL and EPL are simple- or double-acting pilot positioners for proportional control of pneumatic linear actuators. The PPL version accepts a 3–15 psi (0.2–1.0 bar) input signal, while the EPL version accepts 4–20 mA. The positioner compares the control signal with the position of a feedback lever connected to the valve stem and produces an output pressure that acts directly on the actuator diaphragm.
This installation and maintenance manual provides technical data for the PPL and EPL types, general safety information, positioner–actuator coupling for direct and reverse action, and installation on yoke and pillar actuators. It also covers pneumatic and electrical connections, start-up, auto/manual operation, optional restricted pilot valve orifices, split-range adjustment, troubleshooting and spare parts. It notes that EPL-EX models are flameproof/intrinsically safe versions and must be fed by certified electric devices. This manual is written in Italian.
| PPL protection | Waterproof IP 66 |
|---|---|
| PPL input signal | 3–15 psi (0.2–1.0 bar) |
| Supply air pressure | 1.4–7 bar (20–100 psi) |
| Standard stroke | 10–80 mm; single spring |
| PPL ambient temperature | -20 to +80 °C |
| PPL linearity | Within +/- 1.0% F.S. |
| PPL weight | 2.1 kg |
| EPL protection | Waterproof IP 66 |
| EPL input signal | 4–20 mA |
| EPL input safety limits | Ui ≤ 30 V; li ≤ 150 mA; Pi ≤ 0.80 W |
| EPL input impedance | 235 ± 15 Ω |
| EPL electric connections | PG16 on ½” NPT connection |
| EPL ambient temperature | -20 to +70 °C |
| EPL weight | 2.1 kg |
| EPL-EX weight | 2.9 kg |
The PPL positioner accepts a 3–15 psi (0.2–1.0 bar) input signal.
They require an air supply of 1.4 to 7 bar (20 to 100 psi).
The EPL positioner has an ambient temperature range of -20 to +70 °C.
Before maintenance, make sure the positioner is not pressurized.