Power Genex PPL/EPL Series Pneumatic/Electropneumatic Pilot Positioner Installation and Maintenance Manual

Installation and maintenance manual for Power Genex PPL/EPL pneumatic and electropneumatic positioners, covering technical data, mounting and troubleshooting.


Power Genex PPL/EPL Series Pneumatic/Electropneumatic Pilot Positioner Installation and Maintenance Manual - cover page
Brand
Power-Genex
Category
Electro-Pneumatic Positioner
Document type
Service Manual
Language
Italian
Pages
20
File format
PDF
File size
4 MB
Published
17 November, 2026
Updated
17 November, 2026
MD5 checksum
928B04835A2AE9BAB0DBA7A0633E1EDC

About this manual

Power Genex PPL and EPL are simple- or double-acting pilot positioners for proportional control of pneumatic linear actuators. The PPL version accepts a 3–15 psi (0.2–1.0 bar) input signal, while the EPL version accepts 4–20 mA. The positioner compares the control signal with the position of a feedback lever connected to the valve stem and produces an output pressure that acts directly on the actuator diaphragm.

This installation and maintenance manual provides technical data for the PPL and EPL types, general safety information, positioner–actuator coupling for direct and reverse action, and installation on yoke and pillar actuators. It also covers pneumatic and electrical connections, start-up, auto/manual operation, optional restricted pilot valve orifices, split-range adjustment, troubleshooting and spare parts. It notes that EPL-EX models are flameproof/intrinsically safe versions and must be fed by certified electric devices. This manual is written in Italian.

What's inside

  • Description
  • Technical Data Type PPL
  • Technical Data Type EPL
  • General and Safety Information
  • Positioner–Actuator Coupling
  • Installation on Valve
  • Pneumatic and Electric Connections
  • Start-Up
  • Split-Range
  • Troubleshooting

Specifications

PPL protectionWaterproof IP 66
PPL input signal3–15 psi (0.2–1.0 bar)
Supply air pressure1.4–7 bar (20–100 psi)
Standard stroke10–80 mm; single spring
PPL ambient temperature-20 to +80 °C
PPL linearityWithin +/- 1.0% F.S.
PPL weight2.1 kg
EPL protectionWaterproof IP 66
EPL input signal4–20 mA
EPL input safety limitsUi ≤ 30 V; li ≤ 150 mA; Pi ≤ 0.80 W
EPL input impedance235 ± 15 Ω
EPL electric connectionsPG16 on ½” NPT connection
EPL ambient temperature-20 to +70 °C
EPL weight2.1 kg
EPL-EX weight2.9 kg

Frequently asked questions

What input signal does the PPL positioner accept?

The PPL positioner accepts a 3–15 psi (0.2–1.0 bar) input signal.

What supply air pressure range do the positioners require?

They require an air supply of 1.4 to 7 bar (20 to 100 psi).

What is the ambient temperature range for the EPL positioner?

The EPL positioner has an ambient temperature range of -20 to +70 °C.

What safety check is required before maintenance?

Before maintenance, make sure the positioner is not pressurized.