Phocos Any-Grid PSW-H-5kW-230/48V Hybrid Inverter Battery Settings Guide

Guide for connecting Phocos Any-Grid PSW-H-5kW-230/48V hybrid inverters to Pylontech US2000, US3000, Phantom-S, Force L1 and Force L2 battery racks.


Phocos Any-Grid PSW-H-5kW-230/48V Hybrid Inverter Battery Settings Guide - cover page
Brand
Phocos
Category
inverter
Document type
Installation Guide
Language
English
Pages
7
File format
PDF
File size
351 KB
Published
09 November, 2026
Updated
09 November, 2026
MD5 checksum
194311AC2B4C3E0C30C1DCE8B83DF87B

About this manual

This guide from Phocos explains recommended settings and communication connections for operating one or more Any-Grid PSW-H-5kW-230/48V hybrid inverter chargers with Pylontech US2000, US3000, Phantom-S, Force L1 and Force L2 battery racks. It covers requirements, battery sizing, Dip switch settings, communication cable wiring, and the Any-Grid settings menus.

The guide states that installation must be performed by a trained professional and that the Any-Grid and battery racks must be installed according to their respective manuals. It also describes checking successful battery communication and notes warning codes 60, 61, 69 and 70 as specific to lithium battery communication functionality.

What's inside

  • Introduction
  • Requirements
  • System Overview
  • Battery Sizing
  • Battery Settings and Communication Cable Installation
  • Dip Switches location

Specifications

Applicable inverterAny-Grid PSW-H-5kW-230/48V
Battery communication cablePSW-H-BAT-CABLE-PYLON-2 or PSW-H-BAT-CABLE-PYLON
Recommended continuous current per battery rackNot exceed 25 Adc, or 37 Adc for US3000, Force L1 and Force L2
Peak current per battery rack100 Adc peak, or 105 Adc for Force L1/L2
Minimum battery racks per inverterAt least 5, or 4 for US3000, Force L1 and Force L2
Maximum total battery charging current settingMenu 02: 80A
Boost battery charging voltage settingMenu 26: 53.0 Vdc
Floating battery charging voltage settingMenu 27: 52.0 Vdc
Low voltage disconnect settingMenu 29: 47.0 Vdc
Off-Grid to Grid voltage set-pointMenu 12: 48 Vdc or higher
Grid to Off-Grid voltage set-pointMenu 13: 52 Vdc or lower

Frequently asked questions

Which Pylontech battery models are covered by this guide?

The guide covers Pylontech US2000, US3000, Phantom-S, Force L1 and Force L2 battery racks.

Which battery communication cable is required?

The guide lists PSW-H-BAT-CABLE-PYLON-2 or alternatively PSW-H-BAT-CABLE-PYLON.

How many battery racks are needed per Any-Grid inverter?

At least 5 battery racks in parallel are needed, or 4 for the US3000, Force L1 and Force L2.

Which settings menus are overwritten after battery communication is established?

Settings menus 02, 26, 27 and 29 are overwritten once communication with the battery is established.

Download PDF (351 KB)