Guide for connecting Phocos Any-Grid PSW-H-5kW-230/48V hybrid inverters to Pylontech US2000, US3000, Phantom-S, Force L1 and Force L2 battery racks.
This guide from Phocos explains recommended settings and communication connections for operating one or more Any-Grid PSW-H-5kW-230/48V hybrid inverter chargers with Pylontech US2000, US3000, Phantom-S, Force L1 and Force L2 battery racks. It covers requirements, battery sizing, Dip switch settings, communication cable wiring, and the Any-Grid settings menus.
The guide states that installation must be performed by a trained professional and that the Any-Grid and battery racks must be installed according to their respective manuals. It also describes checking successful battery communication and notes warning codes 60, 61, 69 and 70 as specific to lithium battery communication functionality.
| Applicable inverter | Any-Grid PSW-H-5kW-230/48V |
|---|---|
| Battery communication cable | PSW-H-BAT-CABLE-PYLON-2 or PSW-H-BAT-CABLE-PYLON |
| Recommended continuous current per battery rack | Not exceed 25 Adc, or 37 Adc for US3000, Force L1 and Force L2 |
| Peak current per battery rack | 100 Adc peak, or 105 Adc for Force L1/L2 |
| Minimum battery racks per inverter | At least 5, or 4 for US3000, Force L1 and Force L2 |
| Maximum total battery charging current setting | Menu 02: 80A |
| Boost battery charging voltage setting | Menu 26: 53.0 Vdc |
| Floating battery charging voltage setting | Menu 27: 52.0 Vdc |
| Low voltage disconnect setting | Menu 29: 47.0 Vdc |
| Off-Grid to Grid voltage set-point | Menu 12: 48 Vdc or higher |
| Grid to Off-Grid voltage set-point | Menu 13: 52 Vdc or lower |
The guide covers Pylontech US2000, US3000, Phantom-S, Force L1 and Force L2 battery racks.
The guide lists PSW-H-BAT-CABLE-PYLON-2 or alternatively PSW-H-BAT-CABLE-PYLON.
At least 5 battery racks in parallel are needed, or 4 for the US3000, Force L1 and Force L2.
Settings menus 02, 26, 27 and 29 are overwritten once communication with the battery is established.