About this manual

This document is the Chinese user manual for the RDU8DC series DC surge protective device (SPD) from People Electric (人民电器). The device complies with GB/T 18802.31 and protects DC power systems against surges caused by lightning or other transient overvoltages by diverting surge current to ground and limiting the overvoltage. It is intended for power protection in industrial, building, civil aviation, finance, telecommunications, port and other systems.

The manual describes the device's working principle (metal oxide varistors with thermal disconnectors and status indicators), its features such as plug-in modular mounting and a built-in fault disconnector, model designations (RDU8DC-B20 and RDU8DC-B40), technical parameters, environmental conditions for use and storage, wiring and installation diagrams, remote signaling contacts, and warranty terms. This manual is written in Chinese.

What's inside

  • 产品概述 (Product overview)
  • 原理 (Working principle)
  • 特点 (Features)
  • 型号及其含义 (Model designation)
  • 技术参数 (Technical parameters)
  • 使用环境 (Environmental conditions)
  • 使用说明及外型安装尺寸 (Instructions and dimensions)
  • 安装示意图 (Installation diagrams)
  • 保修说明及售后服务 (Warranty and after-sales service)

Specifications

Operating/storage temperature-40°C to +70°C
Mounting35mm DIN rail
Protection ratingIP20
Pollution degreeDegree 2
Altitude≤2000m
StandardGB/T 18802.31

Frequently asked questions

What are the remote signaling contact states of the RDU8DC?

With the indicator green (normal), contact 2-3 is closed and 2-1 is open; with the indicator red (fault), 2-3 is open and 2-1 is closed.

Can the RDU8DC be customized for other voltages or currents?

Yes, the manufacturer states it can customize the product according to different customer voltage and current requirements.