OPTEX FlipX series standard indoor detector installation instructions: mounting, wiring, jumper settings, wide/narrow lens setup and walk test.
This document is the installation instruction sheet for the OPTEX FlipX series indoor detector, standard models FLX-S-ST, FLX-S-ST-BKT, FLX-S-DT-X5, FLX-S-DT-X5-BKT, FLX-S-DT-X8 and FLX-S-DT-X9. It identifies the parts (cover, main unit, base, lens, sponge, and the CW-G2 mounting bracket supplied with "-BKT" models) and describes wall mount without bracket, wall mount with bracket and ceiling mount with bracket, including how to break the wiring knockouts.
The second half covers wiring to the terminal and power cable length limits, jumper pin settings for LED, Wide/Narrow lens, PIR sensitivity and MW sensitivity, the Wide/Narrow lens setting procedure, the walk test, and the technical specifications and dimensions of the unit. It also lists compliance statements and the microwave emission frequency and power for the DT models.
| Detection method | Passive infrared and Microwave |
|---|---|
| Coverage | Wide: 12 m (40 ft.) 85° / Narrow: 18 m (60 ft.) 5° (no MW detection at Narrow) |
| Detection zones | Wide: 76 zones / Narrow: 12 zones |
| Mounting height | 2.0 to 3.0 m (6'7" to 9'8"); 2.4 m (8') recommended |
| Power input | 9.5 to 16 V DC |
| Current draw | 8 mA (normal) / 11 mA (normal), 11 mA (max.) at 12 V DC / 14 mA (max.) at 12 V DC |
| Warm-up period | Approx. 60 s (LED blinks) |
| Alarm/tamper relay output | N.C. 24 V DC 0.1 A max. (resistive load); tamper opens when the cover is removed |
| Dimensions | H: 129.2 x W: 61.5 x D: 50.9 mm |
| Weight | Approx. 90 g (3.17 oz); approx. 105 g (3.7 oz) with bracket approx. 120 g / 135 g |
| Microwave emission (DT models) | 10.525 GHz 15.78 mW e.i.r.p / 10.587 GHz 8.93 mW e.i.r.p / 9.425 GHz 14.50 mW e.i.r.p |
The mounting height range is 2.0 to 3.0 m (6'7" to 9'8"), with 2.4 m (8') recommended.
Set the LED pin to ON, close the cover and walk in the detection area to check the detecting performance via the LED indication; a walk test should be conducted at least once a year.
When Narrow is selected, microwave detection is disabled, and the jumper pin must also be set to Narrow.
The warm-up period is approximately 60 seconds, during which the LED blinks.