Guide to connecting the OMRON CP1H PLC with a CP1W-CIF11 module to Modbus RTU remote I/O, covering wiring, settings and program examples.
This manual explains how to link an OMRON CP1H controller to Modbus RTU remote I/O modules using the CP1W-CIF11 communication module and CX-Programmer software. It first lists the remote I/O module set: the GFMS-RM01S Modbus RTU master, the GFDI-RM01N 16-channel digital input module, the GFDO-RM01N 16-channel digital output module, the GFPS-0202 and GFPS-0303 power modules, and the 0170-0101 RJ45/RS-485 adapter module.
The document then covers the CP1W-CIF11 switch settings for terminating resistor, 2-wire/4-wire wiring and RS control, and the terminal wiring of RDA-/RDB+ to the adapter module. It describes serial port and Serial Gateway configuration in CX-Programmer, the communication register addresses, and a sample program that polls one GFDI-RM01N input and one GFDO-RM01N output. This manual is written in Chinese.
| GFMS-RM01S master controller | Master Modbus RTU, 1 port |
|---|---|
| GFDI-RM01N digital input | Digital input, 16 channels |
| GFDO-RM01N digital output | Digital output, 16 channels / 0.5 A |
| GFPS-0202 power module | 24 V / 48 W |
| GFPS-0303 power module | 5 V / 20 W |
| 0170-0101 adapter module | 8-pin RJ45 female connector / RS-485 interface |
| First GFDI-RM01N register address | 1000 (HEX) |
| First GFDO-RM01N register address | 2000 (HEX) |
The CP1H is combined with the CP1W-CIF11 communication module, and the connection is configured with CX-Programmer software.
Switch 1 sets the terminating resistor, switches 2 and 3 set the wiring type (ON for 2-wire, OFF for 4-wire), and switches 5 and 6 enable RS control.
The first GFDI-RM01N uses register address 1000 (HEX).
In CX-Programmer, open the serial port settings from the PLC menu, set the communication format and baud rate, and select Serial Gateway.