MK MK234A microprocessor overcurrent relay user guide covering indicators, buttons, contacts, soft switches, technical data, and case dimensions.
The MK MK234A is a microprocessor-based numerical overcurrent relay that uses fundamental frequency current measurement for harmonic current rejection. It provides two-element low-set and high-set overcurrent fault protection with definite time characteristic, and its 4-digit panel display shows present load current, recorded fault current for the last tripping, and all relay settings.
The guide describes light indicators, push-button operation, output contacts, soft switches, technical data, connection diagrams, and case dimensions. It also lists setting ranges, auxiliary supply options, trip contact ratings, and mechanical mounting information.
| Rated current | 5 A |
|---|---|
| Frequency | 50 Hz or 60 Hz |
| Burden | < 0.3 VA at In |
| Auxiliary supply (MK234A-240A(6)) | 198~265 VAC |
| Auxiliary supply frequency | 50 Hz or 60 Hz |
| VA rating | 3 VA typical |
| Auxiliary supply (MK234A-110A(6)) | 94~127 VAC |
| Trip contact rated voltage | 250 VAC |
| Continuous carry | 5A (cos j = 1.0) |
| Make and carry for 0.2 s | 30A |
| Expected electrical life | 105 operations |
| Expected mechanical life | 5 x106 operations |
| Low-set setting I> | 0.5 - 6.00 A (10%-120%) |
| High-set setting I>> | 0.50 - 99.9 A (10%-1998%) |
| High-set definite time t>> | 0.05 - 2.5sec |
| Low-set definite time t> | 0.05- 99 sec |
| Mounting | Panel mounting |
| Front panel | Standard DIN 96x96 mm |
| Approximate weight | 0.7 kg |
Press the "TEST" button.
Press the "RESET" button.
It can show present load current, recorded fault current for the last tripping, and all relay settings.
The MK234A incorporates 3 soft switches for system configuration.