Installer and user guide for the Liebert MPX rack power distribution unit, covering installation, configuration, operation, maintenance, and troubleshooting.
This manual covers the Liebert MPX adaptive rack power distribution unit, a modular and scalable PDU built with components including the MPX Power Rail Chassis (PRC), Power Entry Module (PEM), Input Power Cord (IPC), Branch Receptacle Module (BRM), and RPC communications modules.
It provides safety instructions, installation and assembly steps, system functional tests, operating and configuring rack PDU cards, maintenance information, and troubleshooting for Liebert MPX rack PDU components.
| Ambient temperature range | 32°F to 140°F (0°C to 60°C) |
|---|---|
| Relative humidity | 5% to 95%, non-condensing |
| Fixed capacity North America | up to 60A (48A) per phase |
| Fixed capacity Europe | up to 63A per phase |
| Variable capacity North America | up to 30A (24A) per phase |
| Variable capacity Europe | up to 32A per phase |
| MPX PRC power bus channels | five |
No. Connect only one MPX PEM to an MPX PRC; connecting more than one can cause cross-conduction, equipment damage, injury, or death.
No. The MPX PEM is not hot-swappable and must not be removed while input power is connected.
No. The modules do not contain user-serviceable parts, and the Liebert MPX rack PDUs should not be serviced by users.
No. The RPC-1000 and RPC2 communications modules cannot be used together in an array configuration.