Liebert AC8TM Controller Product Specification/Installation Guide

Liebert AC8TM is a product of Liebert, it can control redundant equipment such as multiple thermal management units or pumps


Liebert AC8TM Controller Product Specification/Installation Guide - cover page
Brand
Liebert
Category
Other Electronics
Document type
Installation Guide
Language
English
Pages
4
File format
PDF
File size
452 KB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
29FDFFEFB618434A74C6BD807BBC488C

About this manual

The Liebert AC8 coordinates control of systems with redundant equipment, such as multiple thermal-management units or pumps. It can control stand-by functions and unit rotation, perform testing on stand-by devices, stage operation based on sensor-reading levels, and monitor alarm status of connected devices.

This guide describes the AC8 enclosure, controller inputs and outputs, keypad display, dimensions, wiring specifications, processor, and agency listings. It also lists supported connections, maximum wiring lengths, and transformer module specifications.

What's inside

  • Features
  • AC8 Enclosure
  • Controller Input and Output
  • Keypad Display
  • Dimensions
  • Wiring Specifications
  • Transformer Module Wiring Specifications
  • Specifications
  • Processor
  • Agency Listings

Specifications

Supported devices8 devices with 1 digital input and 1 digital output per device
Zones4 zones with staging for each zone
Analog inputs4 analog inputs, 4-20 mA, one sensor per zone
Programmable digital-relay outputs2
Common-alarm outputs2
EPOP input1
Digital input ratingDry-contact, 24 VDC, 10 mA
Analog input signal4-20 mA
Digital output rating24 VAC at 3 A
Common alarm output rating24 VAC at 3 A
Enclosure dimensions18 x 2-34 x 18 in. (457.2 x 69.85 x 457.2 m)
Weight20.56 lb (9.33 kg)
Enclosure typeNEMA 1
LCD display4-line, 20-character, backlit
Ambient operating environment32 to 104°F (0 to 40°C), 0% to 95% RH, non-condensing
ProcessorMotorola XC68HC812A4
Clock speed16 MHz
Total RAM256 Kb
Total FLASH4 M
Total EEPROM4 K
A/D resolution12 bit
Communication speed14.4 K bps
Clock typeReal-time Clock
Clock batteryLithium (non-replaceable)
Clock battery life7 years, constant, no power
Battery backup typeNickel Cadmium (replaceable)
Battery backup life10 minutes at full load
Digital input/EPOP maximum length750 ft (225 m)
Analog input (2-wire) maximum length750 ft (225 m)
IGM422/SiteScan maximum length1,000 ft (300 m)
EIA485 maximum length3,000 ft (900 m)
RS232 maximum length50 ft (15 m)
24-VAC power maximum length150 ft (45 m)
115-VAC power maximum length150 ft (45 m)
230-VAC power maximum length150 ft (45 m)
Agency listingsUL, CSA, CE, FCC

Frequently asked questions

What devices can the AC8 interface with?

It interfaces with any device that closes an electrical contact.

How many devices, zones, and analog inputs does the controller support?

It supports 8 devices with one digital input and one digital output each, 4 zones, and 4 analog inputs.

What is the ambient operating temperature range?

32 to 104°F (0 to 40°C) at 0% to 95% RH, non-condensing.

How long does the battery backup last?

10 minutes at full load.

Download PDF (452 KB)