The Liebert ITA 16kVA and 20kVA UPS is an online, double‑conversion, modular UPS designed for small data centers, network and precision equipment. It offers features such as parallel operation, high‑frequency topology, intelligent battery management and optional ECO mode to reduce energy consumption.

This manual provides safety warnings, step‑by‑step installation and commissioning procedures for single‑unit and parallel configurations, detailed description of the front and rear panels, operation of the LCD/LED display, common operating tasks, communication options (USB, RS‑232, MODBUS, SNMP), routine maintenance, and a list of optional accessories. This manual is written in Chinese.

What's inside

  • Product Introduction
  • Single‑Unit Installation and Commissioning
  • Parallel Installation and Commissioning
  • Operation Display Panel
  • Common Operations
  • Communication Interfaces
  • Maintenance and Service
  • Optional Accessories
  • Appendices

Specifications

Battery TypeSealed maintenance‑free lead‑acid
Battery Cells30‑40 cells (default 32)
Rated Voltage360 Vdc – 480 Vdc
Battery Charging Power4.5 kW (0 °C‑30 °C)
Transfer Time0 ms
Noise Level≤ 58 dB
Operating Temperature0 °C – 40 °C
Dimensions (W×H×D)435 mm × 130 mm × 750 mm
Net Weight35 kg

Frequently asked questions

What is the maximum allowable leakage current for grounding the UPS?

The grounding leakage current must be between 3.5 mA and 1000 mA.

Can the UPS be used for life‑support equipment?

No. The UPS is intended for commercial and industrial use only and must not be used as a power source for any life‑support equipment.