This manual provides instructions for data communication wiring, RS485 cabling standards, collector installation requirements, parameter settings, cloud…
This document serves as a guide for the data communication and field debugging of the INVT iMars series PV grid-tied inverters. It covers system connection diagrams, RS485 cabling requirements including shielded cable specifications and conduit standards, and specific installation guidelines for the TAOKO data collector to ensure stable communication. This manual is written in Chinese.
| Minimum waterproof box size for collector | 280.5 * 190.3mm (L*W) |
|---|---|
| Minimum distance from transformer for collector | 2 meters |
| Minimum distance from inverter for collector | 1 meter |
| Maximum effective length of daisy-chained devices per collector | 100 meters |
Industrial-grade shielded communication cables or Category 5e shielded network cables must be used.
The waterproof box dimensions (Length*Width) must be at least 280.5 * 190.3mm.
The collector and its waterproof box must not be installed on a sun-facing side; they require a cool, ventilated location.