Hong Run OHR-C600 Series low-voltage reactive power automatic compensation controller user manual covering 16-output compensation control, parameters, and…
Hong Run OHR-C600 Series low-voltage reactive power automatic compensation controllers are used with static capacitor panels (cabinets) at voltage levels of 400 V or 660 V and below. The controller has 16 output channels, uses fundamental power factor and fundamental reactive power for capacitor switching, provides 6 mixed compensation schemes and 12 switching coding methods, and can correctly display fundamental power factor when harmonics are present.
The controller includes RS485/RS232 communication and protection functions such as overvoltage, undervoltage, undercurrent, phase loss, voltage over-distortion, and temperature protection. This user manual covers product introduction, technical parameters, safety precautions, panel and display functions, and parameter settings including data display, parameter viewing and setting, and parameter setting descriptions. This manual is written in Chinese.
| Output channels | 16 |
|---|---|
| Applicable system voltage | 400 V or 660 V and below |
| Auxiliary power supply | AC 220 V or AC 380 V, ±10%, 50/60 Hz, less than 8 VA |
| Power supply frequency | 50 Hz or 60 Hz |
| Power supply voltage fluctuation | ±10% |
| Total power consumption | Less than 8 VA |
| AC voltage input | Rated 220 V (phase voltage) or 380 V (phase voltage) |
| AC current input | Rated 5 A |
| Overload | Voltage: 1.2x continuous, 2x for 30 s; current: 1.2x continuous, 10x for 5 s |
| AC frequency | 45 to 65 Hz |
| Temperature sensor | PT100 |
| Power factor accuracy | 0.5 class |
| Active power accuracy | 1 class |
| Reactive power accuracy | 1.5 class |
| Temperature accuracy (optional) | 3 class |
| Communication interface | RS485/RS232 |
| Baud rate | 1200 to 38400 bps |
| Communication protocol | MODBUS RTU |
| RS485 communication distance | Up to 1 km |
| RS232 communication distance | Up to 15 m |
| Control outputs | Up to 16 switching outputs; relay output AC 250 V/1 A, DC 30 V/1 A |
| Alarm output | 1 alarm output; contact capacity AC 250 V/2 A, DC 30 V/2 A |
| Power-frequency withstand voltage | 2.5 kV AC for 1 min between auxiliary power and input terminal groups |
| Operating temperature | -10 to 50 °C |
| Storage temperature | -10 to 60 °C |
| Humidity | 25% to 85% RH, non-condensing |
| Mixed compensation schemes | 6 |
| Switching coding methods | 12 |
| Standard | JB/T 9663-2013 |
The controller has 16 output channels.
It provides RS485 and RS232 communication interfaces.
It includes overvoltage, undervoltage, undercurrent, phase loss, voltage over-distortion, and temperature protection.
It follows JB/T 9663-2013, Low-Voltage Reactive Power Automatic Compensation Controller.