Hong Run OHR-C600 Series Low-Voltage Reactive Power Automatic Compensation Controller User Manual

Hong Run OHR-C600 Series low-voltage reactive power automatic compensation controller user manual covering 16-output compensation control, parameters, and…


Hong Run OHR-C600 Series Low-Voltage Reactive Power Automatic Compensation Controller User Manual - cover page
Brand
Hong Run
Category
Other Electronics
Document type
User Manual
Language
Chinese
Pages
12
File format
PDF
File size
831 KB
Published
17 November, 2026
Updated
17 November, 2026
MD5 checksum
91AC1E51F14A21849EBFDBFE49A12E6E

About this manual

Hong Run OHR-C600 Series low-voltage reactive power automatic compensation controllers are used with static capacitor panels (cabinets) at voltage levels of 400 V or 660 V and below. The controller has 16 output channels, uses fundamental power factor and fundamental reactive power for capacitor switching, provides 6 mixed compensation schemes and 12 switching coding methods, and can correctly display fundamental power factor when harmonics are present.

The controller includes RS485/RS232 communication and protection functions such as overvoltage, undervoltage, undercurrent, phase loss, voltage over-distortion, and temperature protection. This user manual covers product introduction, technical parameters, safety precautions, panel and display functions, and parameter settings including data display, parameter viewing and setting, and parameter setting descriptions. This manual is written in Chinese.

What's inside

  • Product introduction
  • Technical parameters
  • Safety precautions
  • Installation and use flow
  • Panel and display functions
  • Parameter settings
  • Data display interface
  • Parameter viewing and setting
  • Parameter setting descriptions

Specifications

Output channels16
Applicable system voltage400 V or 660 V and below
Auxiliary power supplyAC 220 V or AC 380 V, ±10%, 50/60 Hz, less than 8 VA
Power supply frequency50 Hz or 60 Hz
Power supply voltage fluctuation±10%
Total power consumptionLess than 8 VA
AC voltage inputRated 220 V (phase voltage) or 380 V (phase voltage)
AC current inputRated 5 A
OverloadVoltage: 1.2x continuous, 2x for 30 s; current: 1.2x continuous, 10x for 5 s
AC frequency45 to 65 Hz
Temperature sensorPT100
Power factor accuracy0.5 class
Active power accuracy1 class
Reactive power accuracy1.5 class
Temperature accuracy (optional)3 class
Communication interfaceRS485/RS232
Baud rate1200 to 38400 bps
Communication protocolMODBUS RTU
RS485 communication distanceUp to 1 km
RS232 communication distanceUp to 15 m
Control outputsUp to 16 switching outputs; relay output AC 250 V/1 A, DC 30 V/1 A
Alarm output1 alarm output; contact capacity AC 250 V/2 A, DC 30 V/2 A
Power-frequency withstand voltage2.5 kV AC for 1 min between auxiliary power and input terminal groups
Operating temperature-10 to 50 °C
Storage temperature-10 to 60 °C
Humidity25% to 85% RH, non-condensing
Mixed compensation schemes6
Switching coding methods12
StandardJB/T 9663-2013

Frequently asked questions

How many output channels does the OHR-C600 controller have?

The controller has 16 output channels.

What communication interfaces does the controller provide?

It provides RS485 and RS232 communication interfaces.

What protection functions are included?

It includes overvoltage, undervoltage, undercurrent, phase loss, voltage over-distortion, and temperature protection.

What standard does the product follow?

It follows JB/T 9663-2013, Low-Voltage Reactive Power Automatic Compensation Controller.

Download PDF (831 KB)