User manual for the Harsen BC7051 charger, describing operation, indicators, adjustable settings, specifications and wiring.
The Harsen BC7051 Charger is an automatically controlled constant variable-current charger designed for charging batteries used in generator starting and operation. It uses constant current until terminal voltage reaches a preset value, then charging current decreases as voltage rises and changes to trickle charging at the threshold voltage. The manual states that the output is pulse voltage and that charging voltage and current are adjustable.
The Harsen BC7051 Charger manual describes status indicators for AC mains, battery connection, charging, low battery voltage, and a blown fuse, plus LOAD VOLTAGE and MAXIMUM CURRENT adjustment potentiometers. It also lists technical characteristics, dimensions, and a typical wiring diagram with an ALARM fault output. This manual is written in Chinese.
| Battery types | 12V, 24V |
|---|---|
| Low battery voltage warning | 10V for 12V; 21V for 24V |
| Low battery stop-charging value | 8V for 12V; 16V for 24V |
| Trickle charge threshold | 10–15V for 12V; 22–33V adjustable for 24V |
| Charging current | 0–5A adjustable |
| Overcurrent protection | >6.3A |
| Input voltage | 220VAC (-15% to +30%) |
| Input frequency | 45Hz–60Hz |
| Power consumption | ≤220W |
| Operating temperature | -20°C to 50°C |
| Overall size | 120 × 100 × 128 mm |
It is designed to charge batteries used for generator starting and operation.
It uses a constant variable-current mode: constant current below the preset terminal voltage, then current decreases as voltage rises and changes to trickle charging at the threshold.
The manual describes AC power, battery connection, charging status, low battery voltage, and blown fuse indicators.
The ALARM output goes low when battery voltage falls below the set value.