Harsen BC7051 Charger User Manual

User manual for the Harsen BC7051 charger, describing operation, indicators, adjustable settings, specifications and wiring.


Harsen BC7051 Charger User Manual - cover page
Brand
Harsen
Category
Battery Charger
Document type
User Manual
Language
Chinese
Pages
2
File format
PDF
File size
111 KB
Published
12 December, 2011
Updated
28 September, 2026
MD5 checksum
12FF6306E7F0D02D64B228664D733732

About this manual

The Harsen BC7051 Charger is an automatically controlled constant variable-current charger designed for charging batteries used in generator starting and operation. It uses constant current until terminal voltage reaches a preset value, then charging current decreases as voltage rises and changes to trickle charging at the threshold voltage. The manual states that the output is pulse voltage and that charging voltage and current are adjustable.

The Harsen BC7051 Charger manual describes status indicators for AC mains, battery connection, charging, low battery voltage, and a blown fuse, plus LOAD VOLTAGE and MAXIMUM CURRENT adjustment potentiometers. It also lists technical characteristics, dimensions, and a typical wiring diagram with an ALARM fault output. This manual is written in Chinese.

What's inside

  • Overview
  • Indicators and Potentiometers
  • Technical Characteristics
  • Dimensions
  • Typical Wiring Diagram

Specifications

Battery types12V, 24V
Low battery voltage warning10V for 12V; 21V for 24V
Low battery stop-charging value8V for 12V; 16V for 24V
Trickle charge threshold10–15V for 12V; 22–33V adjustable for 24V
Charging current0–5A adjustable
Overcurrent protection>6.3A
Input voltage220VAC (-15% to +30%)
Input frequency45Hz–60Hz
Power consumption≤220W
Operating temperature-20°C to 50°C
Overall size120 × 100 × 128 mm

Frequently asked questions

What is the Harsen BC7051 Charger designed for?

It is designed to charge batteries used for generator starting and operation.

How does the BC7051 Charger charge a battery?

It uses a constant variable-current mode: constant current below the preset terminal voltage, then current decreases as voltage rises and changes to trickle charging at the threshold.

What indicators are described in the BC7051 Charger manual?

The manual describes AC power, battery connection, charging status, low battery voltage, and blown fuse indicators.

When does the ALARM output go low?

The ALARM output goes low when battery voltage falls below the set value.

Download PDF (111 KB)

More Harsen Manuals


View all Harsen manuals →