Growatt NSDM630MCT V2 three-phase smart meter quick guide for din-rail installation, RS485 communication, and Growatt inverter connection.
The Growatt NSDM630MCT V2 is a multi-functional din-rail meter for accurate measurement and display of parameters in 3P3W/3P4W power grid systems, such as voltage, current, power, frequency, active power, reactive power, positive energy, reverse energy, and total harmonics. It works with an external current transformer and features an RS485 communication interface supporting Modbus RTU for remote monitoring.
The quick guide covers unpacking, dimensions, installation wiring for voltage sampling, current transformers, and RS485 cables, plus button descriptions for viewing measured values on the panel display.
| Rated voltage | 3×230/400Vac |
|---|---|
| Rated frequency | 50/60Hz |
| Input current range | 1A or 5A |
| Communication | RS485 output for Modbus RTU |
| Baud rate | 9600bps(default) |
| Max. Reading | 9999999.9kWh/kVArh |
| Outline dimensions | 94.5x72x65mm(LxWxH) |
| Protection level | IP51 (indoor) |
The meter provides an RS485 output for Modbus RTU communication.
The default baud rate is 9600bps.
The RS485 cable must be less than 100m, with a recommended length under 25m.