GE HumiTrac XR Transmitter Series Installation Guide

Installation guide for the GE HumiTrac XR transmitter series, covering mounting, wiring, power requirements, and specifications.


GE HumiTrac XR Transmitter Series Installation Guide - cover page
Brand
GE
Category
Temperature sensors
Document type
Installation Guide
Language
English
Pages
2
File format
PDF
File size
255 KB
Published
23 November, 2026
Updated
23 November, 2026
MD5 checksum
038CEF9595838FD57A496621C7643E98

About this manual

This installation guide covers the GE HumiTrac XR transmitter series from GE Sensing & Inspection Technologies. It provides mounting instructions for wall, duct, and outside air installations, plus wiring diagrams and switch settings for voltage and current outputs.

The document lists power requirements of 12–30 VDC, environmental operating and storage ranges, signal outputs, accuracy specifications, and CE compliance information for the capacitive humidity and temperature transmitters.

What's inside

  • Warranty
  • Calibration
  • Power Requirements
  • Installation
  • Environmental Conditions
  • Wiring
  • CE Compliance
  • Contact Information

Specifications

Power supply12–30 VDC
Operating range–40°F to 140°F (–40°C to 60°C)
Storage temperature–67°F to +185°F (–55°C to +85°C)
Sensing elementCapacitive Sensor
Long term stabilityLess than 1% drift per year, typical
Signal outputs4-20 mA, 0-5V or 0-10V (user selectable)
IP ratingIP 42 for Duct Mount and Outside Air Transmitters
WarrantyOne year for sensor tip, two years for rest of product

Frequently asked questions

What power supply does the transmitter require?

A 12–30 VDC power supply furnished by the customer is required.

What is the warranty period?

The sensor tip is warranted for one year and the rest of the product for two years from shipment.

Where should an outside air mount transmitter be located?

It should be located on the north side, ideally under an eave, with the sensor pointing down.

What signal outputs are available?

The outputs are 4-20 mA, 0-5V or 0-10V and are user selectable.