This manual provides installation, usage, and maintenance instructions for the Fanhai Sanjiang J-SAP-M-963K fire hydrant button, including technical…
The Fanhai Sanjiang J-SAP-M-963K fire hydrant button is designed to be connected to an intelligent fire alarm controller via input modules JK-952 or JK-A52. When activated, it sends an alarm signal and closes a normally open contact to trigger the fire pump. The device features a red start indicator and a green response indicator, with a reusable actuator that can be reset using a dedicated tool. This manual is written in Chinese.
| Execution Standard | GB 16806-2006 |
|---|---|
| Working Current (Standby) | 0 mA |
| Working Current (Action) | < 25mA |
| Output Contact Capacity | 0.1A/30VDC |
| Weight | Approx. 112g (with base) |
| Dimensions | 90x90x43 mm (with base) |
| Wiring Method | Two-wire system (TO+, TO-) |
| Operating Temperature | 0°C to +55°C |
The actuator can be reset manually using a dedicated tool after pressing it.
It connects to the intelligent fire alarm controller via input modules JK-952 or JK-A52.
The button should be tested at least once every quarter, and maintenance is recommended annually.