Fanhai Sanjiang GL-957 Short Circuit Isolator User Manual

User manual for the Fanhai Sanjiang GL-957 Short Circuit Isolator, designed for short circuit fault protection in 9000 series fire alarm control systems.


Fanhai Sanjiang GL-957 Short Circuit Isolator User Manual - cover page
Brand
Shenzhen市泛海三江电子
Category
Other Electronics
Document type
User Manual
Language
English
Pages
2
File format
PDF
File size
285 KB
Published
20 December, 2011
Updated
19 October, 2026
MD5 checksum
D5ACDB95C6873140A8658FAA649EE046

About this manual

The Fanhai Sanjiang GL-957 Short Circuit Isolator is a device used for protecting bus lines against short circuit faults. It is specifically designed for use with the 9000 series fire alarm control system. When a short circuit fault occurs at the output end of the device (with a current greater than 400mA), the isolator automatically cuts off all connected equipment to ensure the bus continues to operate normally. Once the fault is repaired, the device automatically restores the connection to the equipment.

What's inside

  • Overview
  • Main Technical Parameters
  • Instructions for Use
  • Installation and Debugging
  • Precautions

Specifications

Operating ModeNon-polarity two-wire system
Static Current<1.0mA
Action Current>400mA
Operating Environment Temperature-10℃~50℃
External Dimensions86 ×86×40mm (with the base)
Weightabout 125g (with the base)
Compatible System9000 series fire alarm control system

Frequently asked questions

Does the GL-957 require coding or address assignment?

No, the short circuit isolator does not need coding and does not occupy an address in the bus circuit.

Can multiple GL-957 isolators be connected in series?

No, the concatenation application of multiple short circuit isolators is not supported.