The KZ-953 output module manual provides specifications, installation, wiring, and usage instructions for the Fanhai Sanjiang fire‑link module.
This manual describes the KZ-953 output module, which works with the 二总线 9000 series controller to control fire‑link devices such as alarm bells. It includes an overview of the module, its features, technical specifications, and safety precautions.
Detailed installation steps, wiring diagrams for both built‑in and external terminal loads, and commissioning procedures are provided. The document also explains how to set the module address, connect the encoder, and verify proper operation through indicator LEDs. This manual is written in Chinese.
| Working mode | Polarity‑free two‑wire |
|---|---|
| Static current | < 0.6 mA |
| Action current | < 10 mA |
| Output current capacity | 2 A @ 30 V DC |
| Operating temperature | -10 °C to 50 °C |
| Relative humidity | ≤ 95% (40 °C ±2 °C, no condensation) |
| Terminal load resistance | 47 kΩ |
| Dimensions | 86 × 86 × 40 mm |
| Weight | ≈125 g |
| Standard | GB16806-2006 |
Connect the module as shown in Figure 3; the built‑in 47 kΩ load is used and the output dry‑node signal is provided after actuation.
The module can supply up to 2 A at 30 V DC.
It operates from –10 °C to 50 °C and up to 95 % relative humidity (40 °C ± 2 °C, no condensation).
Ensure the external 24 V power polarity is correct; reversed polarity can damage the module.